IntelliKnight 5808 Installation Manual 151274-L8
4-17
4.7.4 Dry Contact Wiring
The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch supported by the
control panel can be used with the 5880. For example, you can use a 5880 to monitor pull stations, water flow,
tamper, reset, or silence switches.
Wire dry contacts as shown in Figure 4-20. Notice grouping of terminals; power terminals are shared by two
inputs.
Figure 4-20 Dry Contact Wiring
Model 7628
Supervised/Power Limited
4.7k
EOL