4.12 On-Board Programmable Relays (Conventional)
The control panel has two built-in programmable relays and a built-in trouble relay. All relays are Form C rated
at 2.5 A @ 24 VDC (resistive).
Figure 4-30 Location of Conventional Relay Circuits
Note: The N.C. contact is the relay contact that is closed when the panel has power and there are no alarm or
trouble conditions.
4.12.1 Trouble Relay
The control panel has a dedicated common Form C trouble relay built into terminals labeled TROUBLE. The
relay provides a normally open and a normally closed contact. The trouble relay will deactivate under any trouble
condition.
4.12.2 Programmable Relays
The control panel has two Form C programmable relays built into terminals labeled RELAY 1 and RELAY 2.
Each relay provides a normally open and a normally closed contact.
To install one or two programmable relays, follow these steps.
1. Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4-30 for the location of the relay ter-
minals.
2. Configure the relay through programming (see section 7.5).
4.13 Remote Station Applications
4.13.1 Keltron Model 3158 Installation
The control panel is compatible with Keltron Model 3158, used for direct connection to a Keltron receiver. The
3158 reports alarms, supervisories, and troubles.
The steps for connecting the 3158 to the control panel. Refer to the 3158 installation instructions for complete
information.
1. Wire the 3158 to the control panel as shown in the connection list and Figure 4-31.
2. Wire the 3158 within 20 feet of the control panel. Wiring must be enclosed in conduit.
3. Program control panel Relay 2 for alarm.
Connect to Power
Limited Sources only