User Manual

SK and SD SLC Device Installation 151274-L8
5-2
5.2 List of SD SLC Devices
The following SD SLC devices can be used with the control panel. See the appropriate section number in this
manual or the device installation instructions (packaged with the device) for more information.
Note: The control panel supports the use of either SD SLC devices or SK SLC devices. You cannot install both
SLC device types on this control panel.
5.3 Maximum Number of Devices
The 5808 supports SK or SD devices on one 5808 system. The maximum number of devices per system varies
depending on device protocol. Device support is as follows:
SK Devices–A 5808 system can support a total of 99 SK detectors and 99 SK modules.
OR
SD Devices–A 5808 system can support a total of 127 SD SLC detectors and modules, in any combination.
5.4 Wiring Requirements for SLC Devices
The following information applies to all SLC devices. Refer to the section that describes the type of device you
are installing for details.
SD
Model Number
Model Name/Description
Section / Install
Sheet PN
SD505-APS Photoelectric smoke detector.
Section 5.7
SD505-AIS Ionization smoke detector
SD505-AHS Absolute temperature heat detector. Trip point range from 135°F–150°F (0°C–37°C).
SD505-6AB 6" base for use with the SD505-AHS, SD505-AIS, and SD505-APS. 150955
SD505-6IB 6" short circuit isolator base for use with the SD505-AHS, SD505-AIS, and
SD505-APS
151175
SD505-6RB 6" relay base for use with the SD505-AHS, SD505-AIS, and SD505-APS 151192
SD505-6SB 6" sounder base for use with the SD505-AHS, SD505-AIS, and SD505-APS SLC
devices
151191
SD505-DUCT Duct Smoke Detector. Duct Housing including the SD505-APS Analog Photoelectric
Smoke Sensor. Intake tubing for duct available in three lengths:
SD505-T2 (2.5 foot); SD505-T5 (5 foot); SD505-T10 (10 foot)
1700-09882
SD505-DUCTR Duct Detector housing with relay base. Duct housing with relay base including
SD505-APS Analog Photoelectric Smoke detector pre-installed
1700-09882
SD500-PS/-PSDA Single or dual action addressable pull station 151177
SD500-AIM Addressable input module (switch input), standard size, DIP switch configured 151071
SD500-MIM Mini input monitor module (switch input), small size, DIP switch configured. Fits in
single-gang box with manual pull station switch.
151071
SD500-ANM Addressable notification module 151109
SD500ARM Addressable relay module DIP switch configured. 151091
SD500-SDM Addressable smoke detector module. Use to assign an address to a loop of
conventional devices.
151193
SD500-LIM Line isolator module. Fits in a double gang box. 151125
SD500-LED Addressable LED driver module. Capable of driving up to 80 LEDs. Up to 40 SD500-
LED Driver Modules can be used per SLC loop.
151232
SD505-DTS-K Remote test switch & LED indicator for the SD505-DUCTR 1700-09882