IntelliKnight 5808 Installation Manual 151274-L8
5-5
Note: No t-taps allowed on class A SLC loops.
5.5 SK Detector Installation
This section describes how to install heat and smoke detectors. All detectors ship with installation instructions.
Refer to the detector’s installation instructions for more detailed information.
This information applies to the following SK models:
SK-Photo Photoelectric Smoke Detector
SK-Photo-T Photoelectric Smoke Detector with Thermal
SK-Acclimate Photoelectric Smoke Detector with Thermal
SK-Heat Fixed Temperature Detector
SK-Heat-T High Temperature Thermal Detector
SK-Heat-ROR Rate-of-Rise Thermal Detector
SK-ION Ionization Smoke Detector
SK-FIRE-CO CO Smoke Detector
5.5.1 Wiring SK detectors:
1. Wire device bases as shown in Figure 5-4.
2. Set the address for each device as described in Section 5.6.
Figure 5-4 Heat and Smoke Detector Connection to the Panel.
Caution
For proper system supervision do not use looped wire under terminals marked SLC + and – of the SLC device connectors.
Break wire runs to provide supervision of connections.