User Manual

Programming Overview 151274-L8
6-2
1 using constant on output when an alarm condition occurs.
Circuit 5 (Relay 1):
Assigned to Group 124. JumpStart automatically programs Zone 1 to activate Group 124 using constant on
output when a supervisory condition occurs.
Circuit 6 (Relay 2):
Assigned to Group 125. JumpStart automatically programs Zone 1 to activate Group 125 using constant on
output when an alarm occurs.
Addressable output points (Relay modules, NAC Modules, Sounder Bases, Relay Bases):
All addressable relay devices will be configured as "Output Pt" (general purpose output point) and assigned to
Group 1.
Note: Relay output is constant even if the zone activating the relay is programmed with an output pattern.
6.1.3 Running JumpStart AutoProgramming
Run JumpStart immediately after you have addressed and connected all input devices (detectors, pull stations,
and so on) and output devices (notification appliances, relays, and so on).
Note: If you need to install a few devices after you have run JumpStart, you can install them manually. Follow
instructions in Section 7 for configuration.
To run JumpStart, follow these steps.
1. Press
ENTER to view the Main Menu.
2. From the Main Menu Select 7 for the Program Menu.
3. From the next menu, select 6 for JumpStart.
4. The message "WARNING Will DELETE all system options" displays on the LCD. Select Yes to continue. A
series of messages displays for the next several seconds. JumpStart scans the SLC loops for devices. This
can take several minutes, depending on the number of devices attached.
5. When the message, “SLC FAMILY” flashes. Press
ENTER to accept SK, or press up arrow to change to SD and
press
ENTER to accept.
6. When the message “Configuring System Done” displays, press any key to continue.