User Manual

IntelliKnight 5808 Installation Manual 151274-L8
6-3
7. Select one of the following options from the menu that displays.
1 - Review System Press 1 if you need to review the JumpStart configuration.
2 - Repeat JumpStart Press 2 if you need to rerun JumpStart for any reason.
3 - Accept Config. 1. If you are ready to make the JumpStart configuration permanent, select 3.
2. The system will ask you if the installation contains duct detectors. If there are none, select 2 for
No and skip to Step 8. If the system contains duct detectors, select 1 for Yes and continue with
Step 3.
3. From the list that displays, select the SLC device that contains the duct detectors.
4. The first photoelectric or ionization detector on the system will display. Select 1 for DUCT and
2 for NonDUCT.
5. Press to select the next detector. Select 1 for DUCT and 2 for NonDUCT. Continue until
all duct detectors have been selected. (Note: You can move backwards through the list with
).
6. When you reach the last detector on this device, press .
7. The system will ask you if there are more duct detectors in the system. If there are, select 1 for
Yes and repeat from Step 3. If there are no more duct detectors, select 2 for No and continue
with Step 8.
8. The system will restart in 10 seconds. You can press 1 to restart immediately.
9. After the system resets, it will use the new JumpStart configuration.
4 - Enter Programing To go directly to Program mode to configure any devices, press 4. The Programming menu appears
and you can begin programming