Integration Guide

REV070219
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 5 |
batteries than calculated, special care must be taken with the inverter settings to limit the load below the
specified rating of the PHI battery. These settings are described in the following sections of this
Integration Guide.
3.2 - Charge Calculation: Charge Controller Power Bank
Sizing
To optimize solar harvesting, a properly sized PHI battery bank should be able to accept the maximum
PV charge current. To determine the minimum number of PHI batteries required to optimize PV, divide
the output of the charge controller(s) by the “max continuous charge current” per PHI battery. Be sure to
verify the “max continuous charge current” for the PHI battery model that you’re using, because it may
differ from C/2 depending on model.
Charge Example: B
#PV
≥ I
PVChrgMax
/ I
BatChrgMax
Max. continuous charge current for PHI 3.8 48V = 37.5A
PV charge controller max = 80A
B
#PV
≥ 80A / 37.5A = 2.13
A properly sized PHI battery bank based on available PV charge would have a minimum of 3
batteries. This maximizes the use of available PV while ensuring the batteries are never stressed by
overcharging. If the PHI battery bank has fewer batteries than calculated, special care must be taken with
the inverter settings to limit the charge rate below the specified rating of the PHI battery. These settings
are described in the following sections of this Integration Guide.
In summary: When comparing the same system using these two calculations for sizing the PHI
battery bank, the minimum number of batteries should be the greater of the two results (Discharge
Calculation & Charge Calculation). In this example, this translates into 4 PHI batteries in the
system.
4.0 Program Settings for PHI Batteries
In order to maintain the Warranty, it is critical to ensure that the appropriate settings for the desired Warranty
are programmed in all of the system components. This section will cover the basic concepts and settings
for Schneider Electric equipment.
4.1 Depth of Discharge
In order to optimize performance and the life of your system and PHI batteries, SimpliPhi Power
recommends programming the equipment settings for 80% Depth of Discharge (DoD). This qualifies for
the SimpliPhi 10-year / 10,000 cycle Warranty on the batteries. Greater DoD is possible but will result in
reduced cycle life. Refer to the PHI 3.8 kWh Battery Warranty to compare DoD settings and the
associated Warranty.
CAUTION: If a firmware update is executed on Schneider Electric equipment, ALL the settings
must be reverified. The programmed settings shown in the following tables must be applied
based on desired Warranty/Cycle life. The recommended is 80% depth of discharge.