Installation Manual
Damage to the inverter due to moisture ingress during electrical installation
• Never open the inverter when it is raining or snowing, or the humidity is over 95%.
• For attaching the conduits to the enclosure, only use UL-listed rain-tight conduit fittings or UL-
listed conduit fittings for wet locations complying with UL514B.
• Seal all unused openings tightly.
Electrical installations
All electrical installations must be carried out in accordance with the local standards and the
National Electrical Code
®
ANSI/NFPA 70 or the Canadian Electrical Code
®
CSA C22.1.
• Before connecting the inverter to the utility grid, contact your local grid operator. The
electrical connection of the inverter must be carried out by qualified persons only.
• Ensure that no cables used for electrical connection are damaged.
6.2 Overview of the Connection Area
6.2.1 View from Below
A
C
FB
ED
G
Figure 7 : Enclosure openings at the bottom of the inverter
Position Designation
A Enclosure opening for the DC connection (for 27mm (1in) conduits)
B Enclosure opening for the DC connection (for 27mm (1in) conduits)
C Enclosure opening for the connection cables of the Antenna Extension Kit (optional)
and, if needed, for other data cables (for 21mm (0.75in) conduits)
D Enclosure opening for the network cables and, if needed, for other data cables (for
21mm (0.75in) conduits)
E Enclosure opening for the connection cables of the outlet and, if necessary, for the
switch for the secure power supply operation (for 21mm (0.75in) conduits)
F Enclosure opening for the AC connection (for 27mm (1in) conduits)
G Enclosure opening for the AC connection (for 27mm (1in) conduits)
6 Electrical Connection
SMA Solar Technology America LLC
Installation manualSB5.0-6.0-1SP-US-40-IA-xx-1026