Installation Manual

Position Designation
P Equipment grounding terminals for the equipment grounding conductors of the PV
array
Q Communication assembly
R
DISPLAY socket for connecting the display cable
6.3 AC Connection
6.3.1 Requirements for the AC Connection
Additionally required material (not included in the scope of delivery):
Conduits: 27mm (1in) or smaller with a proper reducing bush
Rain-tight conduit fittings for wet locations complying with UL 514B: 27mm (1in) or smaller
with a proper reducing bush
Requirements for the AC conductors:
The conductors must be approved for temperatures of over +75°C (+167°F).
The conductors with regards to its ampacity, rated temperatures, operating conditions and its
power loss must be made in accordance with the local standards and the National Electrical
Code
®
ANSI/NFPA 70 or the Canadian Electrical Code
®
CSA C22.1.
Conductor type: copper wire
The conductors must be made of solid wire, stranded wire or finely stranded wire. When using
finely stranded wire, bootlace ferrules must be used.
Conductor cross-section: 6mm² to 16mm² (10AWG to 6AWG)
Load-break switch an cable protection
Damage to the inverter due to the use of screw-type fuses as load-break switch
Screw-type fuses are not load-break switches.
Do not use screw-type fuses as load-break switches.
Use a load-break switch or a circuit breaker for load disconnection.
In PV systems with multiple inverters, protect each inverter with its own overcurrent protective
device. Observe the maximum permissible fuse protection (see Section10 "Technical Data",
page61). This will prevent residual voltage from being present at the corresponding cable
after disconnection.
The load-break switch or circuit breaker must be listed (see National Electrical Code
®
ANSI/
NFPA 70).
Loads installed between the inverter and the overcurrent protective device must be fused
separately.
The overcurrent protective device for the AC output circuit is to be provided by others.
6 Electrical Connection
SMA Solar Technology America LLC
Installation manualSB5.0-6.0-1SP-US-40-IA-xx-1028