Installation Manual

Procedure:
1.
Danger to life due to high voltages
When exposed to sunlight, the PV array generates dangerous DC voltage which is present in
the DC conductors. Touching the DC conductors can lead to lethal electric shocks.
If an external DC disconnecting switch is available, open the external DC disconnecting
switch.
If there is no external DC disconnecting switch, cover the PV modules with opaque
material (e.g. foil).
Ensure that the DC load-break switch on the inverter is in the O position.
Ensure that there is no voltage on the DC cables of the PV array.
2. Remove the adhesive tape from the enclosure opening for the DC connection and, if other
enclosure openings are to be used, take the sealing plugs out of these enclosure openings.
3. Insert the conduit fitting into the opening and tighten from the inside using the counter nut.
4. Attach the conduit to the conduit fitting.
5. Guide the conductors from the conduit into the inverter. In the process, lay the conductors in
the inverter such that they do not come into contact with the communication assembly.
6. Connect each equipment grounding conductor of the PV array to an equipment grounding
terminal:
Strip the insulation of the equipment grounding conductor by 18mm (0.71in).
Thread the screw through the spring lock washer, the clamping bracket and the washer.
Guide the equipment grounding conductor
between the washer and clamping bracket
and tighten the screw with a Torx
screwdriver (TX 25) (torque: 6Nm ±
0.3Nm (53.10in-lb ± 2.65in-lb)). Here,
the equipment grounding conductor must
have contact with an inner edge of the
clamping bracket.
If two equipment grounding conductors are
to be connected to one equipment
grounding terminal, guide both equipment
grounding conductors between the washer
and clamping bracket and tighten the screw
with a Torx screwdriver (TX 25) (torque:
6Nm ± 0.3Nm (53.10in-lb ± 2.65in-lb)).
Here, every equipment grounding
conductor must have contact with an inner
edge of the clamping bracket.
7. Plug the connecting terminal plate for the DC connection into the DC-in slot in the inverter.
While doing so, only touch the connecting terminal plate on the black enclosure.
6 Electrical Connection
SMA Solar Technology America LLC
Installation manualSB5.0-6.0-1SP-US-40-IA-xx-1034