Installation Manual

Conductor cross-section: 0.2mm² to 2.5mm² (24 AWG to 14AWG)
The conductor type and wiring method must be appropriate for the application and location.
Procedure:
1. Remove the sealing plug from the opening for connecting the switch for secure power supply
operation.
2. Insert the conduit fitting into the opening and tighten from the inside using the counter nut.
3. Attach the conduit to the conduit fitting.
4. Guide the conductors from the conduit into the inverter.
5. Strip off the conductor insulation by max. 10mm (0.4in).
6. Connect the conductors to the plug. When doing
so, ensure that the conductors are completely
plugged into the conduit entries up to their
insulation.
7. Stick the plug into the SPS slot on the
communication assembly in the inverter.
D-IN
SPS
A B
FCC ID: SVF-KP20
IC: 9440A-KP20
8. Ensure that the plug is securely in place.
9. Ensure that all conductors are correctly connected.
10. Ensure that the conductors sit securely in the terminals.
Useful hint: To release the conductors from the plugs, open the conduit entries using a suitable
tool.
6 Electrical Connection
SMA Solar Technology America LLC
Installation manualSB5.0-6.0-1SP-US-40-IA-xx-1044