Installation Manual

Rated grid volt-
age
Triggering
threshold - Trig-
gering voltages
Triggering volt-
age - Neutral
conductor
Triggering volt-
age - L1 and L2
Tripping time
208V 50% 57.6V to 62.4V 99.8V to
108.2V
max. 0.1602s
88 % 103.2V to
108.0V
178.9V to
187.2V
max. 2.002s
110 % 129.6V to
134.4V
224.6V to
233.0V
max. 1.001s
120 % 141.6V to
146.4V
245.4V to
253.8V
max. 0.1602s
240V 50% 57.6V to 62.4V 115.2V to
124.8V
max. 0.1602s
88 % 103.2V to
108.0V
206.4V to
216.0V
max. 2.002s
110 % 129.6V to
134.4V
259.2V to
268.8V
max. 1.001s
120 % 141.6V to
146.4V
283.2V to
292.8V
max. 0.1602s
Measuring precisions:
Triggering threshold: ±2% of the rated grid voltage
Tripping time: ±1% of the nominal tripping time
Triggering frequency: ±0.2% of rated power frequency
General Data
Width x height x depth 535mmx730mmx198mm
(21.1 in x 28.7 in x 7.8 in)
Weight 26 kg (57.32 lbs)
Length x width x height of the packaging 800mmx600mmx300mm
(31.5in x 23.6in x 11.8in)
Transport weight 30 kg (66.14 lbs)
Operating temperature range -25°C to +60°C (-13°F to +140°F))
Storage temperature -40°C to +60°C (-13°F to +140°F))
Maximum permissible value for relative humid-
ity, non-condensing
95 %
Maximum operating altitude above mean sea
level (MSL)
3000 m
10 Technical Data
SMA Solar Technology America LLC
Installation manual 63SB5.0-6.0-1SP-US-40-IA-xx-10
ENGLISH