User's Manual

Electrical Connection SMA Technologie AG
Page 42 SMC50A_60A-IEN073320 Installation Guide
5 Connect the protective earth (PE) of the
mains cable to the right terminal of the
terminal block (see figure to the right).
To do this, the PE wire must be 5 mm longer
than the L and N wires!
PE conductor connection
If a second protective earth connection is required, you can use
the additional connection terminal directly on the Sunny Mini
Central's housing for this purpose.
Proceed as follows:
1. Insert the terminal clamp in the slits and
screw the terminal half tight with the
supplied M6x16 screw and washer.
The toothing of the washer must face
toward the terminal clamp.
2. Insert the stripped grounding cable.
3. Secure the terminal tightly.
6 Connect the mains cable as shown in the
figure. Use the supplied cable feed-through.
"L" and "N" must not be swapped!
"L" and "N" connection
Step Instruction
PE
L
N