Specification Sheet

196
TXD 14 AND 15
DAMPER
OD
ROOF
OPENING
CURB
OD
A B C D
FAN
WT
SHIP
WT
18 19-1/4 22-1/4 31-1/2 23 24 2 85 120
R
®
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
AIR
PERFORMANCE
SOUND
and
TXD 15
TXD 14
CFM / BHP @ Static Pressure / Sones
HP RPM
Tip
Speed
0 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 1-1/4
Catalog Num-
ber
983
.04/3.6
680
.05/3.1
338
.04/16
- - - - - - - TXD-1425SC 1/4 650 2514
1058
.05/4.4
784
.06/3.9
461
.06/3.6
- - - - - - - TXD-1425SC 1/4 700 2707
1134
.06/5.2
884
.07/4.7
580
.07/4.4
298
.10/4.2
- - - - - - TXD-1425SC 1/4 750 2901
1210
.07/5.9
980
.08/5.3
697
.09/5.1
424
.10/4.8
- - - - - - TXD-1425SC 1/4 800 3094
1285
.09/6.5
1073
.10/6.1
810
.10/5.9
547
.10/5.6
303
.08/5.4
- - - - - TXD-1425SC 1/4 850 3287
1361
.10/7.3
1164
.11/6.8
920
.12/6.6
667
.10/6.4
430
.11/6.1
- - - - - TXD-1425SC 1/4 900 3481
1436
.12/8.1
1253
.13/7.7
1026
.14/7.4
784
.10/7.2
554
.13/6.9
338
.11/6.9
- - - - TXD-1425SC 1/4 950 3674
1512
.14/8.9
1340
.15/8.5
1129
.16/8.2
900
.20/8.1
676
.16/7.8
466
.14/7.6
262
.10/7.6
- - - TXD-1425SC 1/4 1000 3868
1918
.11/7.6
1702
.12/6.8
1414
.13/6.0
1065
.13/6.0
- - - - - - TXD-1550SC 1/2 795 3359
2135
.15/9.0
1948
.17/8.2
1710
.18/7.5
1406
.18/7.1
1087
.17/7.5
- - - - - TXD-1550SC 1/2 885 3739
2352
.20/10.5
2188
.22/9.8
1983
.23/9.1
1736
.24/8.6
1444
.24/8.6
1145
.23/9.5
- - - - TXD-1550SC 1/2 975 4119
2461
.23/11.3
2305
.25/10.6
2114
.26/9.9
1888
.27/9.4
1616
.28/9.1
1349
.27/10.0
981
.24/11.2
- - - TXD-1550SC 1/2 1020 4310
2569
.26/12.1
2422
.28/11.4
2241
.30/10.8
2034
.31/10.2
1787
.32/9.7
1522
.31/10.6
1239
.30/11.7
777
.24/13.1
- - TXD-1550SC 1/2 1065 4500
2786
.33/13.9
2653
.36/13.2
2491
.38/12.6
2313
.39/12.0
2104
.40/11.5
1863
.41/11.8
1623
.40/12.9
1362
.38/14.2
969
.33/15.7
- TXD-1550 1/2 1155 4880
3443
1.30/31
3372
1.31/30
3299
1.31/29
3222
1.32/29
3141
1.33/28
3055
1.33/27
2964
1.34/26
2866
1.33/26
2758
1.33/26
2508
1.30/25
TXD1515 1-1/2 1760 7055
MODEL TXD
DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER
UL STANDARD 705 for Electrical
UL STANDARD 762 for
Grease Removal
Performance certied is for installation type A - free inlet, free outlet.
Performance ratings include the effects of birdscreen.
The sound ratings shown are loudness values in fan sones @ 5' (1.5m) in a hemispherical
free eld calculated per AMCA Standard 301. Values shown are for: Installation Type A: free
inlet hemispherical sone levels.
Base Unit - AMCA Seal does not apply to units with speed control (bolded).
SC RPM range capable with solid state speed control.
Speed (RPM) shown is nominal. Performance is based on actual speed of test.
S&P USA Ventilation Systems, LLC.,
Div. of Soler & Palau Ventilation Group
certies that the Models TXD shown
herein are licensed to bear the AMCA
Seal. The ratings shown are based
on test and procedures performed in
accordance with AMCA Publication 211
and AMCA Publication 311 and comply
with the requirement of the AMCA
Certied Ratings Program.