Specification Sheet

25
MODEL PV
INLINE CENTRIFUGAL DUCT FAN
Air Performance
Model
No.
Nom.
RPM
Volts
Max.
Watts
CFM v Static Pressure (SP) Ins. WG
Max.
SP
Duct
Dia.
Ins.
0” 0.125” 0.25” 0.375” 0.5” 0.75” 1.0” 1.25” 1.5”
PV-100 1400 115 57 108 100 92 85 78 66 52 33 18 1.70 4”
PV-100x 2880 115 84 153 142 130 120 111 96 80 63 34 1.85 4”
PV-125 2350 115 58 128 104 85 74 63 47 32 15 - 1.43 5”
PV-125x 2745 115 85 206 190 170 153 135 110 88 62 33 1.77 5”
PV-150 2750 115 78 245 205 177 157 129 93 59 - - 1.20 6”
PV-150x 2700 115 130 390 367 340 312 285 233 193 153 110 2.05 6”
PV-200 3100 115 130 402 375 350 327 296 239 179 135 85 1.94 8”
PV-200x 2930 115 180 544 515 485
446 415 360 312 273 230 2.64 8”
PV-250 3000 115 170 568 533 502 471 440 370 312 263 221 2.61 10”
PV-250x 3045 115 214 618 595 570 540 510 450 390 340 297 2.80 10”
PV-315 2600 115 170 654 605 570 525 487 408 333 265 203 2.21 12.4”
PV-315x 2650 115 370 942 905 859 811 762 622 508 440 390 3.90 12.4”
Performance certied is for installation type D-Ducted inlet, Ducted outlet. Performance ratings do not include the effects of appurtenances
(accessories). Speed (RPM or RPS) shown is nominal. Performance is based on actual speed of test.
Dimensions in inches/mm
Model A B C D E F G
Weight
lbs(kgs)
PV-100
3
13/16
97.5
3
13/16
97.5
4
3/4
120
7
11/16
196
7
1/2
190
4
3/4
120
9
9/16
243
7
3.0
PV-100x
3
13/16
97.5
3
13/16
97.5
4
3/4
120
7
11/16
196
7
1/2
190
4
3/4
120
9
9/16
243
7
3.0
PV-125
4
13/16
122.5
4
13/16
122.5
4
3/4
120
7
13/16
198
7
1/2
190
4
3/4
120
9
9/16
243
7
3.0
PV-125x
4
13/16
122.5
4
13/16
122.5
4
3/4
120
7
13/16
198
7
1/2
190
4
3/4
120
9
9/16
243
7
3.0
PV-150
5
13/16
147
5
13/16
147
4
3/4
120
8
7/16
214
9
5/16
236
4
3/4
120
13
1/8
334
11
5.0
PV-150x
5
13/16
147
5
13/16
147
4
3/4
120
8
7/16
214
9
5/16
236
4
3/4
120
13
1/8
334
11
5.0
PV-200
7
13/16
198
7
13/16
198
4
3/4
120
8
3/4
223
9
5/16
236
4
3/4
120
13
1/8
334
11
5.0
PV-200x
7
13/16
198
7
13/16
198
4
3/4
120
8
3/4
223
9
5/16
236
4
3/4
120
13
1/8
334
11
5.0
PV-250
9
3/4
248
9
3/4
248
4
3/4
120
8
1/16
205
9
5/16
236
4
3/4
120
13
1/8
334
13
6.0
PV-250x
9
3/4
248
9
3/4
248
4
3/4
120
8
1/16
205
9
5/16
236
4
3/4
120
13
1/8
334
13
6.0
PV-315
12
5/16
312
12
5/16
312
4
3/4
120
9
3/16
233
10
9/16
269
4
3/4
120
15
13/16
401
21
10.0
PV-315x
12
5/16
312
12
5/16
312
4
3/4
120
9
3/16
233
10
9/16
269
4
3/4
120
15
13/16
401
21
10.0
Sound
Fan sound levels are measured in sones. At this time there are no sone level test standards available through HVI due to the fact that remote mounted fan noise levels
are in proportion to the following: type of duct, length of duct, fan distance from the intake source and other random factors. It is generally accepted that remote mounted
venting is usually quieter than standard (in room) venting.
S&P USA Ventilation Systems,
LLC., Div. of Soler & Palau
Ventilation Group, certies that
the PV range shown herein is
licensed to bear the AMCA Seal.
The ratings shown are based on
tests and procedures performed
in accordance with AMCA
Publication 211 and comply with
the requirements of the AMCA
Certied Ratings Program.
*PV 150x and
larger ENERGY
STAR
®
qualied.
The PV-POWERVENT Series
fans are California Title 24
compliant and meet ASHRAE
62.2 when installed with 3
way switch and remotely
mounted speed control.
PERFORMANCE/DIMENSIONS