Specification Sheet

262
PERFORMANCE/DIMENSIONS
SQD 60
Motor HP
CFM / Sones @ Static Pressure
RPM
0 1/8 1/4 3/8 1/2 5/8 3/4 1
100 WATT
2700 RPM
.95 Max
Amps @
115/60/1
151
1.9
93
1.0
- - - - - - 950
199
3.4
162
2.5
102
2.2
- - - - - 1250
238
4.6
208
3.7
174
3.5
116
3.4
- - - - 1500
294
6.6
269
5.6
245
5.4
215
5.3
170
5.2
130
5.1
- - 1850
334
8.1
312
7.1
290
6.8
268
6.7
240
6.6
201
6.5
158
6.5
- 2100
382
10.1
362
9.2
343
8.6
324
8.5
304
8.5
281
8.4
250
8.3
176
8.3
2400
424
12.0
406
11.1
389
10.4
372
10.3
355
10.2
337
10.2
316
10.1
257
10.0
2700*
Unit Specications
• 18 Ga. galvanized housing.
Approximate unit weight 30 lbs.
Aluminum backward inclined wheel.
(SQD 60 has composite wheel)
Removable access panels.
• Integral inlet & outlet duct collars.
AMCA Licensed Air & Sound.
• Disconnect switch.
• Universal/any angle mounting.
SQD 610
Motor HP
CFM / BHP / Sones @ Static Pressure
RPM
0 1/8 1/4 3/8 1/2
1/10 HP
1550 RPM
198
.01/2.3
109
.01/1.8
- - - 950
229
.01/3.3
158
.01/3.0
- - - 1100
260
.01/4.8
200
.01/4.6
115
.01/4.1
- - 1250
291
.01/5.8
239
.01/5.6
174
.01/5.2
- - 1400
322
.02/6.8
276
.02/6.7
222
.02/6.3
150
.02/5.9
- 1550
343
.02/7.5
300
.02/7.3
251
.02/7.1
190
.02/6.7
- 1650
357
.03/8.0
316
.03/7.8
269
.03/7.6
214
.02/7.2
137
.02/6.8
1710*
* Base Unit-AMCA seal for sound Rating does not apply to units with speed control installed.
+ RPM range capable with solid state speed control.
Speed (RPM) shown is nominal. Performance is based on actual speed of test.
Performance certied is for installation type B - free inlet, ducted outlet.
Power Ratings (BHP) does not include drive losses.
Performance ratings do not include the effects of appurtenances in the airstream.
The sound ratings shown are loudness values in fan sones @ 5' (1.5m) in a hemispherical
free eld calculated per AMCA Standard 301. Values shown are for installation type A - free
inlet fan sone levels.
R
®
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
AIR
PERFORMANCE
SOUND
and
S&P USA Ventilation Systems, LLC., Div.
of Soler & Palau Ventilation Group, certies
that the Models SQD shown herein are
licensed to bear the AMCA Seal. The ratings
shown are based on test and procedures
performed in accordance with AMCA Pub-
lication 211 and AMCA Publication 311 and
comply with the requirement of the AMCA
Certied Ratings Program.
MODEL SQD & eSQD
DIRECT DRIVE SQUARE INLINE CENTRIFUGAL DUCT FAN
STANDARD 705