Specification Sheet

317
Model L3
Size 72
Limits
Panel OD
Square
Min. Wall
Opening
Damper
OD
Approx.
Wt
Model RPM
Motor
Frame
L3 545 256T 80 81 1/2 78 1/2 600
Size
Motor
HP
Max
BHP
Fan
RPM
Sones
(0.00” SP)
Static Pressure (Inches W.G)
.000 .125 .200 .250 .300 .375 .500 .625 .750 1.000
Level 3 Construction
Model L3 72
1 1/2
1.29 225 22 35129 20805 - - - - - - - -
1.50 235 23 36690 23490 11736 - - - - - - -
1.77 250 25 39032 28557 16766 - - - - - - -
2
2.00 260 27 40593 30797 19872 12185 - - - - - -
2.23 270 28 42154 33105 22720 15591 - - - - - -
2.36 275 29 42935 34370 23988 17268 - - - - - -
3
3.00 295 34 46058 38778 28928 23480 16818 - - - - -
3.22 305 36 47619 40624 32722 26224 20149 - - - - -
3.54 315 39 49180 42421
35839 28644 23303 - - - - -
5
4.26 335 44 52303 45927 40304 34243 28943 20547 - - - -
5.00 350 48 54645 48505 44011 39490 32581 25385 - - - -
5.98 375 56 58548 52752 49397 45162 40602 32470 19719 - - -
7
6.44 385 60 60109 54439 52140 47621 43710 34888 23115 - - -
7.50 405 64 63232 57793 54820 52395 48197 39949 29577 17215 - -
8.71 425 67 66354 61123 58310 56291 52989 47294 35402 24005 - -
10
10.00 445 69 69477 64435 61744 59908 57687 52162 40392 30620 19305 -
11.04 460 71 71819 66908 64294 62555 60633 55471 44092 35242 24397 -
12.15 475 74 74160 69373 66838 65165 63387 59202 48920 39535 29471 -
15
15.00 510 79 79625 75100
72720 71154 69590 66984 59376 48219 40396 -
16.41 525 81 81967 77547 75223 73700 72190 69767 62695 52353 44585 26079
18.36 545 85 85089 80799 78545 77078 75619 73370 67480 59891 49467 32867
Performance ratings do not include the effects of appurtenances (accessories).
Power ratings (BHP) do not include transmission losses.
Performance certied is for installation type A-free inlet, free outlet.
The sound ratings shown are loudness values in fan sones @ 5' (1.5m) in a hemispherical free eld calculated per AMCA Stan-
dard 301. Values shown are for installation Type A-Free inlet fan sone levels.
Due to air stream cooling, the motor loading into the service factor shown does not overheat the motor and is within NEMA
recommended limits. BHP at most static pressure points is less than the maximum power shown - in many cases substantially
less. Use Optisizer to see the exact BHP for your selection.
R
®
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
AIR
PERFORMANCE
SOUND
and
S&P USA Ventilation Systems, LLC., Div.
of Soler & Palau Ventilation Group, certies
that the models shown herein are licensed to
bear the AMCA Seal. The ratings shown are
based on test and procedures performed in
accordance with AMCA Publication 211 and
AMCA Publication 311 and comply with the
requirement of the AMCA Certied Ratings
Program.
Standard 705
(Optional)
MODELS LCE/LCS, L2E/L2S, L3E/L3S
BELT DRIVE SIDEWALL PROPELLER FANS