Specification Sheet

354
S&P USA Ventilation Systems, LLC.,
Div. of Soler & Palau Ventilation Group,
certies that the Models HRED-C shown
herein are licensed to bear the AMCA
Seal. The ratings shown are based
on test and procedures performed in
accordance with AMCA Publication 211
and comply with the requirement of the
AMCA Certied Ratings Program.
Model
HRED-C
CFM / BHP @ Static Pressure
HP RPM
Sones
@ 5 ft.
0 1/8 1/4 3/8 1/2 5/8 3/4
24
5991 / 0.541 5222 / 0.607 4453 / 0.617 2966 / 0.597 2203 / 0.609 1/2 870 16.1
6908 / 0.867 6081 / 0.86 5194 / 0.854 3735 / 0.831 2780 / 0.842 1193 / 0.851 3/4 870 18
5219 / 0.325 4327 / 0.384 3555 / 0.398 2526 / 0.381 1709 / 0.363 1/3 1160 19.7
6390 / 0.570 5597 / 0.622 4739 / 0.627 3798 / 0.617 2572 / 0.617 1297 / 0.606 1/2 1160 21
7394 / 0.892 6553 / 0.902 5687 / 0.893 4861 / 0.874 3918 / 0.884 2755 / 0.892 1715 / 0.983 3/4 1160 23
8361 / 1.237 7480 / 1.247 6758 / 1.248 6041 / 1.239 5084 / 1.215 3481 / 1.239 2323 / 1.258 1 1160 24
8800 / 1.662 8133 / 1.726 7560 / 1.746 6979 / 1.736 6254 / 1.710 4759 / 1.694 4216 / 1.694 1-1/2 1160 25
7115 / 0.896 6567 / 1.021 5995 / 1.045 5406 / 1.102 4802 / 1.106 4138 / 1.114 3369 / 1.083 1 1750 31
9535 / 1.697 8870 / 1.719 8189 / 1.728 7487 / 1.721 6759 / 1.714 5990 / 1.683 5159 / 1.686 1-1/2 1750 43
10288 / 2.216 9673 / 2.306 9112 / 2.342 8574 / 2.349 8042 / 2.343 7494 / 2.346 6924 / 2.337 2 1750 37
30
8058 / 0.597 6645 / 0.627 5130 / 0.612 3974 / 0.570 1/2 870 16.9
8885 / 0.852 7507 / 0.891 6113 / 0.888 5383 / 0.878 4050 / 0.838 2400 / 0.858 3/4 870 19.7
10095 / 1.255 8508 / 1.256 7085 / 1.208 5837 / 1.185 4593 / 1.149 3590 / 1.140
2116 / 1.186 1 870 20
11015 / 1.890 9970 / 1.890 8893 / 1.874 8361 / 1.849 7542 / 1.690 5640 / 1.721 4904 / 1.750 1-1/2 870 21
12350 / 2.621 11159 / 2.505 9333 / 2.460 7529 / 2.408 8180 / 2.307 6815 / 2.642 5793 / 2.352 2 870 24
9274 / 0.860 8023 / 0.886 6518 / 0.863 4673 / 0.820 2755 / 0.816 3/4 1160 25
10694 / 1.267 9425 / 1.257 7878 / 1.231 6528 / 1.159 4811 / 1.140 2873 / 1.216 1 1160 29
12020 / 1.923 10870 / 1.924 9633 / 1.896 8269 / 1.849 7103 / 1.815 6316 / 1.821 5272 / 1.778 1-1/2 1160 30
12847 / 2.523 11665 / 2.545 10635 / 2.542 9601 / 2.517 8715 / 2.493 7782 / 2.446 6963 / 2.324 2 1160 33
14635 / 3.789 13612 / 3.698 12046 / 3.592 10947 / 3.559 10069 / 3.537 9085 / 3.531 8146 / 3.391 3 1160 37
12938 / 2.463 12151 / 2.534 11337 / 2.536 10304 / 2.536 9364 / 2.532 8331 / 2.501 7503 / 2.464 2 1750 46
15195 / 3.850 14454 / 3.896 13595 / 3.898 12668 / 3.900 11692 / 3.826 10813 / 3.791 9585 / 3.667 3 1750 54
36
10708 / 0.780 9073 / 0.833 7377 / 0.845 5612 / 0.808 3/4 870 22
12730 / 1.152 11041 / 1.200 9168 / 1.184 7346 / 1.169 5061 / 1.101 1 870 26
13685 / 1.745 12339 / 1.718 10479 / 1.629 8588 / 1.591 6455 / 1.569 3906 / 1.606 1-1/2 870 30
16374 / 2.409 14844 / 2.388 13309 / 2.392 11779 / 2.312 10037 / 2.191 7404 / 2.162 4676 / 2.102 2 870 28
18199 / 3.466 16805 / 3.322 15502 / 3.285 14102 / 3.277 12081 / 3.118 9540 / 3.143 6836 / 3.268 3
870 32
14053 / 1.744 12929 / 1.849 11650 / 1.865 10402 / 1.895 9167 / 1.882 7833 / 1.845 6471 / 1.769 1-1/2 1160 34
14679 / 2.115 13505 / 2.186 12290 / 2.221 10972 / 2.206 9636 / 2.189 8405 / 2.172 7148 / 2.158 2 1160 35
17582 / 3.577 16319 / 3.541 15067 / 3.534 13775 / 3.523 12491 / 3.523 11275 / 3.512 9950 / 3.487 3 1160 37
21936 / 5.769 20539 / 5.574 19232 / 5.503 17980 / 5.498 16773 / 5.523 15581 / 5.523 14152 / 5.480 5 1160 47
15035 / 3.422 14138 / 3.515 13355 / 3.547 12613 / 3.550 11869 / 3.544 11060 / 3.555 10171 / 3.448 3 1750 74
20465 / 5.422 19705 / 5.639 18927 / 5.770 18129 / 5.832 17312 / 5.843 16476 / 5.826 15609 / 5.903 5 1750 75
24839 / 8.311 24078 / 8.482 23262 / 8.608 22392 / 8.685 21480 / 8.718 20544 / 8.716 19609 / 8.663 7-1/2 1750 81
Performance shown is for Installation Type A: Free inlet, Free outlet. BHP does not include drive losses.
PERFORMANCE DATA - HRED-C DIRECT DRIVE
MODELS HREB-C & HRED-C
HOODED PROPELLER ROOF EXHAUST FANS