Specification Sheet

396
PERFORMANCE/DIMENSIONS
Max. Motor Frame: 145T
Shaft Size: 5/8"
Housing Gauge: 16
Approximate Weight: 90 lbs.
Flange Holes: 6
Diameter Flange Holes: 7/16”
Finish: Epoxy Coated
Galvanized
A B C E B.C.D.
12-3/8 14-1/2 12* 21 13-1/2
A: ID B: OD C: Length E: Max. Height
*Motor may extend past unit
Standard 705
MODEL TDB
BELT DRIVE TUBEAXIAL DUCT FAN
HP RPM
Static Pressure (Inches W.G.)
0 0.125 0.25 0.375 0.5
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
1/4
1550 1358 0.20 1189 0.20 - - - - - -
1600 1402 0.21 1240 0.23 914 0.22 - - - -
1650 1445 0.24 1291 0.25 1021 0.24 - - - -
1700 1489 0.26 1341 0.27 1104 0.27 - - - -
1/3
1725 1511 0.27 1365 0.28 1141 0.28 - - - -
1775 1555 0.29 1414 0.31 1210 0.31 - - - -
1825 1599 0.32 1463 0.33 1274 0.34 - - - -
1875 1642 0.35 1511 0.36 1335 0.36 - - - -
1/2
1925 1686 0.37 1559 0.39 1393 0.39 1001 0.38 - -
2000 1752 0.42 1630 0.43 1478 0.44 1211 0.43 - -
2075 1818 0.47
1700 0.48 1559 0.49 1341 0.49 - -
2150 1883 0.52 1771 0.54 1638 0.55 1450 0.55 - -
3/4
2200 1927 0.56 1817 0.58 1690 0.59 1516 0.59 - -
2275 1993 0.62 1887 0.64 1767 0.65 1609 0.65 1324 0.63
2350 2059 0.68 1956 0.70 1842 0.71 1698 0.72 1474 0.71
2425 2124 0.75 2025 0.77 1916 0.78 1783 0.79 1593 0.78
Size 12
R
®
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
AIR
PERFORMANCE
SOUND
and
S&P USA Ventilation Systems, LLC., Div. of
Soler & Palau Ventilation Group certies that
the Models TDB shown herein are licensed to
bear the AMCA Seal. The ratings shown are
based on test and procedures performed in
accordance with AMCA Publication 211 and
AMCA Publication 311 and comply with the
requirement of the AMCA Certied Ratings
Program.
Performance certied is for installation type A - free inlet, free outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (BHP) does not include transmission losses.
E
B.C.D.
B
A
.436
Dia.
Front View
C
Side View
Air Flow