Specification Sheet

51
Choosing the Right Size TR or TRC by Air Handler Load
For each ton of air handling capacity, 120 CFM of Energy Recovery Ventilation is recommended.
MODEL TR AND TRC SIZING
Ton
Capacity 30%
Outside Air
Fraction in
CFM
Model
Needed
1.0 120 TR130
1.6 192 TR200
2.0 244 TR300
2.5 299 TR300
3.0 360 TRC500
3.5 415 TRC500
4.0 490 TRC500
5.0 594 TRC800
6.8 810 TRC800
9.3 1,116 TRC1600
14.3 1,716 TRC1600
Models TR130,
TR200 and TR300
Model TRC500 Model TRC800
Choosing the correct size TR for your structure is easy, all you
need to know is the square footage.
If you structure is up to:
1500 Sq. Ft. you need a TR90/TR90G
2700 Sq. Ft. you need a TR130
4000 Sq. Ft. you need a TR200
6000 Sq. Ft. you need a TR300
Choosing the Right Size TR by Square Footage
MODELS TR & TRC
TOTAL RECOVERY FOR ALL CLIMATES
Models
TR90/TR90G
Model TRC1600