Specification Sheet

58
TR200
Blowers
34" Line Cord
Interlock Switch
Energy Transfer Core
Filters
24 Volt AC
Control Terminal
Line Cord
RA
OA
FA
EA
23 7/8"
20 1/8"
41 1/2" Service Access
11 7/8"
11 7/8"
5 1/2"
5 1/2"
9 1/8"
6"
6"
8 1/8"
6"
8"
28 3/4"
FRONT VIEW
RIGHT VIEW
TOP VIEW
Ventilation Type: Static Plate, Heat and Humidity Transfer
Typical Airow Range: 100-200 CFM
Unit may be mounted in any orientation
Number Motors: One, 0.1 hp
V Hz Phase Input Watts FLA
120 60 Single 157 @ 181 CFM 1.5
Control Voltage: 24 VAC transformer / relay package with
switched dry contacts
Filters: MERV 8, spun polyester media. 10-1/2” x 21-3/4” x 1”
Weight: 70 lbs (unit), 82 lbs (in carton)
Shipping Dimensions: 32” L x 21-1/2” W x 29” H (in carton)
Options:
SPTL - Percentage Timer Control
SPBL - Push Button Point-of-Use Control
SFM Percentage Timer Control with Furnace Interlock
SHW-20 - Dehumidistat Control
Airow
CFM
ESP in
H
2
O
Temp
EFF%
Total EFF%
Winter/Summer*
122 0.70 81 77/64
149 0.60 79 75/61
168 0.50 78 73/59
176 0.40 78 72/59
186 0.30 77 72/58
192 0.20 77 71/57
207 0.10 76 70/56
* Contact Factory for HVI certication report for complete certied rating.
EA: Exhaust Air to outdoors
OA: Outdoor Air intake
RA: Room Air to be exhausted
FA: Fresh Air to inside
LISTED
DUCTED HEAT
RECOVERY VENTILATOR
89S5
Specications
Performance
Dimensions
MODEL TR
TOTAL RECOVERY FOR ALL CLIMATES