Specification Sheet

69
AHRI 1060-2005 - CERTIFIED PERFORMANCE
Energy recovery components certied in accordance with AHRI Standard 1060-2005.
Actual Performance in packaged equipment may vary.
AHRI-1060 Certied Performance - Model Number L85-G5 (used in TRC500)
Type Tilt Angle Nominal Airow Pressure Drop
Plate N/A
100% - 450 SCFM 0.6 in. H
2
O
75% - 338 SCFM 0.5 in. H
2
O
Leakage Ratings Thermal Effectiveness Ratings at 0” Pressure Differential
Pressure
Differential
EATR OACF
Purge Angle
or Setting
Nominal
Airow
Sensible Latent Total
Net
Airow
Net
Sensible
Net
Latent
Net
Total
Test 1 -1 in. H
2
O 1.0% 1.00 N/A
450
CFM
Heating
73% 53% 66%
450
CFM
73% 53% 66%
Cooling
73% 46% 56% 73% 46% 56%
Test 2 0 in. H
2
O 0.0% 1.02 N/A
338
CFM
Heating 77% 60% 71%
338
CFM
77% 60% 71%
Test 3 1 in. H
2
O 0.0% 1.05 N/A
Cooling 77% 52% 61% 77% 52% 61%
AHRI-1060 Certied Performance - Model Number L125-G5 (used in TRC800 & TRC1600)
Type Tilt Angle Nominal Airow Pressure Drop
Plate N/A
100% - 750 SCFM 0.65 in. H
2
O
75% - 563 SCFM 0.45 in. H
2
O
Leakage Ratings Thermal Effectiveness Ratings at 0” Pressure Differential
Pressure
Differential
EATR OACF
Purge Angle
or Setting
Nominal
Airow
Sensible Latent Total
Net
Airow
Net
Sensible
Net
Latent
Net
Total
Test 1 -1 in. H
2
O 1.0% 1.00 N/A
750
CFM
Heating 71% 52% 64%
750
CFM
71% 52% 64%
Cooling 71% 43% 53% 71% 43% 53%
Test 2 0 in. H
2
O 0.0% 1.02 N/A
563
CFM
Heating 75% 59% 69%
563
CFM
75% 59% 69%
Test 3 1 in. H
2
O 0.0% 1.05 N/A
Cooling 75% 50% 59% 75% 50% 59%
NOTE: SCFM = Standard Cubic Feet per Minute OACF = Outdoor Air Correction Factor EATR = Exhaust Air Transfer Ratio N/A = Not Applicable
MODEL TRC
TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS
MODEL TRC
TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS