Specification Sheet
Table Of Contents
69
AHRI 1060-2005 - CERTIFIED PERFORMANCE
Energy recovery components certied in accordance with AHRI Standard 1060-2005.
Actual Performance in packaged equipment may vary.
AHRI-1060 Certied Performance - Model Number L85-G5 (used in TRC500)
Type Tilt Angle Nominal Airow Pressure Drop
Plate N/A
100% - 450 SCFM 0.6 in. H
2
O
75% - 338 SCFM 0.5 in. H
2
O
Leakage Ratings Thermal Effectiveness Ratings at 0” Pressure Differential
Pressure
Differential
EATR OACF
Purge Angle
or Setting
Nominal
Airow
Sensible Latent Total
Net
Airow
Net
Sensible
Net
Latent
Net
Total
Test 1 -1 in. H
2
O 1.0% 1.00 N/A
450
CFM
Heating
73% 53% 66%
450
CFM
73% 53% 66%
Cooling
73% 46% 56% 73% 46% 56%
Test 2 0 in. H
2
O 0.0% 1.02 N/A
338
CFM
Heating 77% 60% 71%
338
CFM
77% 60% 71%
Test 3 1 in. H
2
O 0.0% 1.05 N/A
Cooling 77% 52% 61% 77% 52% 61%
AHRI-1060 Certied Performance - Model Number L125-G5 (used in TRC800 & TRC1600)
Type Tilt Angle Nominal Airow Pressure Drop
Plate N/A
100% - 750 SCFM 0.65 in. H
2
O
75% - 563 SCFM 0.45 in. H
2
O
Leakage Ratings Thermal Effectiveness Ratings at 0” Pressure Differential
Pressure
Differential
EATR OACF
Purge Angle
or Setting
Nominal
Airow
Sensible Latent Total
Net
Airow
Net
Sensible
Net
Latent
Net
Total
Test 1 -1 in. H
2
O 1.0% 1.00 N/A
750
CFM
Heating 71% 52% 64%
750
CFM
71% 52% 64%
Cooling 71% 43% 53% 71% 43% 53%
Test 2 0 in. H
2
O 0.0% 1.02 N/A
563
CFM
Heating 75% 59% 69%
563
CFM
75% 59% 69%
Test 3 1 in. H
2
O 0.0% 1.05 N/A
Cooling 75% 50% 59% 75% 50% 59%
NOTE: SCFM = Standard Cubic Feet per Minute OACF = Outdoor Air Correction Factor EATR = Exhaust Air Transfer Ratio N/A = Not Applicable
MODEL TRC
TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS
MODEL TRC
TOTAL RECOVERY FOR ALL CLIMATES - COMMERCIAL APPLICATIONS