Product Brochure

Size (AWG
or kcmil)
No. of strands 60°C 75°C 90°C
14* 1 15 4 102 15 15 15 15 AC
12* 1 15 4 119 23 20 20 20 AC
10* 1 20 4 150 36 30 30 30 AC
14* 19 15 4 109 16 15 15 15 AC
12* 19 15 4 128 24 20 20 20 AC
10* 19 20 4 161 38 30 30 30 AC
8 19 30 5 213 63 40 50 55 ABCD
6 19 30 5 249 95 55 65 75 ABCD
4 19 40 6 318 152 70 85 100 ABCD
3 19 40 6 346 189 85 100 115 ABCD
2 19 40 6 378 234 95 115 130 ABCD
1 19 50 7 435 299 110 130 145 ABCD
1/0 19 50 7 474 372 125 150 170 ABCD
2/0 19 50 7 518 462 145 175 195 ABCD
3/0 19 50 7 568 575 165 200 225 ABCD
4/0 19 50 7 624 718 195 230 260 ABCD
250 37 60 8 694 851 215 255 290 ABCD
300 37 60 8 747 1012 240 285 320 ABC
350 37 60 8 797 1174 260 310 350 ABC
400 37 60 8 842 1334 280 335 380 ABC
500 37 60 8 926 1655 320 380 430 ABCD
600 61 70 9 1024 1987 350 420 475 ABC
750 61 70 9 1126 2464 400 475 535 BC
1000 61 70 9 1275 3257 455 545 615 C
Package
Codes:
A - 2500' Reel
B - 1000' Reel
C - 500' Spool
D - 5000' Reel
* Sizes 14, 12, and 10 AWG are available with SIMpull® Technology only in SIMpull® Barrel or CoilPAK® configurations. Standard put ups
vary from the ones shown on this chart for standard 14-10 AWG THHN.
+Allowable ampacities shown are for general use as specified by the 2014 Edition of the National Electrical Code Sections 310.15 and
240.4(D).
Unless the equipment is marked for use at higher temperatures the conductor shall be limited to the following per NEC 110.14(C):
60° C - When terminated to equipment for circuits rated 100 amperes or less or marked for 14 - 1 AWG conductors.
75° C - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90° C - THHN dry locations and THWN-2 wet or dry locations for ampacity adjustment purposes using NEC section 310.15.
Standard
Package
Jacket
Thickness
(mils)
Conductor
Insulation
Thickness
(mils)
Nominal
O.D.
(mils)
Approx.
Net Wt.
Per
1000'
(lbs.)
Allowable Ampacities+