Product Brochure

RECOMMENDED SAMPLE SPECIFICATIONS:
Cable shall be UL-listed Type UF-B, suitable for operation at 600 volts or less in all installations as specified in the National Electrical Code.
Conductors shall be annealed copper as manufactured by Southwire Company or approved equal.
Size (AWG
or kcmil)
No. of
strands
Insulation
and jacket
thickness
(mils)
Size
(AWG)
No. of
strands
14 1 19 30 14 1 423X168 70 15 AC
12 1 19 30 12 1 463X183 95 20 ACDE
12 1 19 30 386X183 70 20 AC
10 1 24 30 10 1 518X215 138 30 ACDE
8 7 35 45 10 1 678X302 222 40 BCE
6 7 35 45 10 1 770X338 303 55 BCE
14 1 19 30 14 1 581X168 95 15 AC
12 1 19 30 12 1 626X183 129 20 ACD
12 1 19 30 581X183 107 20 A
10 1 24 30 10 1 727X215 191 30 ABC
8 7 35 45 10 1
1059X319
344 40 BCE
6 7 35 45 10 1
1223X361
478 55 BCE
Ground Wire
Allowable
Ampacity
TWO CONDUCTOR
Conductor
Jacket
Thickness
(mils)
Cable
Dimension
(mils)
Approx.
Net Wt.
Per
1000'
(lbs.)
Standard
Package
+ Ampacities per National Electrical Code section 310.15 and 340.80, 2011 Edition
Package Code:
A-250'
B-500'
C-1,000'
D-2,500'
E-125'
THREE CONDUCTOR
Without Ground
Without Ground