Product Brochure

RECOMMENDED SAMPLE SPECIFICATIONS:
SER Sample Specification: Cable shall be UL-listed Type SE, Style SER, suitable for operation at 600 volts or less as specified in the
National Electrical Code. Conductors shall be AlumaFlex TM aluminum alloy, weather resistant PVC jacketed, as manufactured by
Southwire Company or approved equal. SEU Sample Specification: Cable shall be UL-listed Type SE, Style SEU, suitable for
operation at 600 volts or less as specified in the National Electrical Code. Conductors shall be AlumaFlex TM aluminum alloy, weather
resistant PVC jacketed, as manufactured by Southwire Company or approved equa
Conductor
Size/Const. AWG or kcmil
Phase
Conductor &
Neutral
Equipment
Ground
Conductor
60°C 75°C 90°C Dwelling
6-6-6 7 - 650 40 50 60 - 150 B
4-4-4 7 - 745 55 65 75 - 203 B
4-4-6 7 - 745 55 65 75 - 203 B
2-2-2 7 - 864 75 90 100 100 290 B
8-8-8-8 1 1 612 30 40 45 - 136 B
6-6-6-6 7 7 717 40 50 60 - 196 B
4-4-4-6 7 7 823 55 65 75 - 252 B
2-2-2-4 7 7 956 75 90 100 100 359 B
1-1-1-3 8 7 1079 85 100 115 110 449 C
1/0-1/0-1/0-2 10 1 1168 100 120 135 125 540 C
2/0-2/0-2/0-1 12 1 1264 115 135 150 150 652 C
3/0-3/0-3/0-1/0 16 1 1371 130 155 175 175 786 C
4/0-4/0-4/0-2/0 19 1 1496 150 180 205 200 960 C
250-250-250-3/0 22 1 1839 170 205 230 225 1458 C
2-2-2-2-4 6 7 1059 75 90 100 100 452 B
2/0-2/0-2/0-2/0-1 12 1 1404 115 135 150 150 827 C
4/0-4/0-4/0-4/0-2/0 19 1 1672 150 180 205 200 1228 C
250-250-250-250-3/0 22 1 1847 170 205 230 225 C
SER Aluminum Three Conductor With Bare Ground (Formerly referred to as "Four Conductor")
SER Aluminum Four Conductor With Bare Ground (Formerly referred to as "Five Conductor")
SER Aluminum Two-Conductor With Bare Ground (Formerly referred to as "EZ-SE")
Standard
Package
Stranding
Approximate
Net Weight
Per 1000'
(Lbs)
Nominal
O.D.
(Mils)
Allowable Ampacities
Conductor
Size/Const. AWG or kcmil
Phase
Conductor &
Neutral
Equipment
Ground
Conductor
60°C 75°C 90°C Dwelling
6-6-6 7 8 430x687 40 50 60 - 145 B,C,E
4-4-4 7 12 499x800 55 65 75 - 198 B
4-4-6 7 15 474x775 55 65 75 - 181 B
2-2-2 7 14 569x925 75 90 100 100 283 B,C,G
2-2-4 7 18 554x910 75 90 100 100 259 B,C,G
2/0-2/0-2/0 18 18 736x1221 115 135 150 150 514 C
2/0-2/0-1 18 14 720x1205 115 135 150 150 468 C
4/0-4/0-4/0 18 18 878x1462 150 180 205 205 765 C
4/0-4/0-2/0 18 18 835x1419 150 180 205 205 691 C
Table values reflect XHHW-2 conductors. Allowable ampacities shown are for general use as specified by the National Electrical
Code, 2011 Edition, Section 310.15.
60°C - When terminated to equipment for circuits rated 100 amperes or less or marked for 14 through 1 AWG conductors. See
NEC Article 338.10 (B)(4).
75°C - When terminated to equipment for circuits rated 100 amperes or marked for conductors larger than 1 AWG conductors.
May not apply, see NEC Article 338.10 (B)(4).
90°C - Wet or dry locations. For ampacity de-rating purposes.
Dwelling - For units, conductors shall be permitted at listed ampacities as 120/240-volt, 3-wire, single-phase services and feeders
per NEC Article 310.15.
*For compact-stranded construction, the number of wires, as permitted by UL Standard 854 and ASTM B-801 may be reduced as
follows: 19-wire constructions - 18 wires minimum.
Package
B - 1,000'
E-250'
G-200'
SEU Aluminum Two Conductor With Bare Conentric Ground (Formerly referred to as "Three Conductor")
Stranding
Nominal O.D.
(Mils)
Allowable Ampacities
Approximate
Net Weight
Per 1000'
(Lbs)
Standard
Package