Product Brochure

RECOMMENDED SAMPLE SPECIFICATIONS:
Conductors shall be UL-listed Type NM-B, suitable for operation at 600 volts in all installations as specified in the National Electrical Code. SIMpull ®
jacketed conductors shall be annealed copper as manufactured by Southwire Company or approved equal.
Size (AWG
or kcmil)
No. of
conductors
No. of strands
Size
(AWG)
No. of
strands
14 2 1 19 14 1 360X162 57 15 BEF
12 2 1 19 12 1 410X179 82 20 BEF
10 2 1 24 10 1 494X210 124 30 ABE
8 2 7 35 10 1 612X269 186 40 ABCD
6 2 7 35 10 1 683X304 225 55 BDF
14 3 1 19 14 1 307 74 15 BDF
12 3 1 19 12 1 347 107 20 BEF
10 3 1 24 10 1 422 164 30 BCE
8 3 7 35 10 1 565 253 40 ABCD
6 3 7 35 10 1 650 357 55 ABCD
4 3 7 46 8 1 814 560 70 BCD
2 3 7 46 8 1 952 816 95 BCD
14 2/2 1* 19 14 1 336 91 15 BE
14 4 1** 19 14 1 336 91 15 BE
12 2/2 1* 19 12 1 381 132 20 BE
12 4 1** 19 12 1 381 132 20 BE
10
4
1
24
10
1
465
201
30
BE
+ Ampacities per National Electrical Code section 310.15 and 334.80, 2011 Edition
NOTE: Jacket thickness for all NM-B cable is 30 mils
* Color code for 2/2 conductor cable is Black, White, Red and White with Red stripe.
** Color code for 4 conductor cable is Black, White, Red and Blue.
PACKAGE CODE:
A-2,500'
B-1,000'
C-500'
D-125'
E-250'
F-500'
Conductor
Insulation
Thickness
(mils)
Approx.
Cable
Dimension
(mils)
Approx.
Net Wt.
Per 1000'
(lbs.)
Standard
Package
Ground Wire
Allowable
Ampacity
+
TWO CONDUCTOR
THREE CONDUCTOR
FOUR CONDUCTOR