Product Brochure

16-3 Triplex 600V Secondary UD
Triplex 600V
Secondary UD
Aluminum Conductors. Cross-linked Polyethylene (XLP) Insulation.
APPLICATIONS
Used for secondary distribution and underground service at 600 volts or less, either direct burial or in ducts.
SPECIFICATIONS
Southwire's triplex or paralleled 600 volt secondary UD cable meets or exceeds the following applicable ASTM specifications:
B-230 Aluminum 1350-H19 Wire for Electrical Purposes.
B-231 Aluminum 1350 Conductors, Concentric-Lay-Stranded.
B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes.
B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire.
Southwire's triplex 600 volt secondary UD cable meets or exceeds all applicable requirements of ICEA S-105-692 for
cross-linked polyethylene insulated conductors and UL Standard 854 for Type USE-2.
CONSTRUCTION
Conductors are stranded, compressed 1350-H19, H16, or H26 aluminum, insulated with vulcanized interlinked polyethylene
(VIP
1
), Southwire's cross-linked polyethylene. Neutrals are triple yellow extruded stripe. Cables with "YES" neutrals have
sequential footage markers. Conductors are durably surface printed for identification. Two phase conductors and one neutral
conductor are cabled together to produce the triplex cable configuration. Conductors are also available paralleled.
1
VIP is a registered trademark of Southwire Company for cross-linked polyethylene(XLP).
Wed Feb 17 11:26:14 EST 2010 Page 1 of 2