Other Fuels:
The Detector will react to other fuels in standard fire conditions at maximum
response time of 3 seconds.
The sensitivity range to other fuels varies according to the fuel type. Table 1
below provides the sensitivity to other fuels relative to (as a percentage of) the
sensitivity to a standard gasoline fire source.
Table 1. Response Sensitivity Ranges
Type of Fuel % of Max. Distance at Each
Sensitivity Range
Gasoline 100%
N-Heptane 100%
Alcohol 95% 75%
JP4 75%
Kerosene 75%
Diesel Fuel 75%
Methane Fire* 30%
Propane Fire* 30%
* 0.5m plume fire