Manual

SharpEye
TM
Single IR Flame Detector User Guide
6 Principles of Operation
1.4.5 Product Certification
The 40/40R Flame Detectors have the following certifications:
ATEX, IECEx, page 6
FM, CSA, page 6
SIL-2 Approved (TÜV), page 6
EN54-10, page 6
1.4.5.1 ATEX, IECEx
The 40/40R Optical Flame Detector is certified to:
ATEX Ex II 2 GD per SIRA 07ATEX 1149 and IECEx SIR. 07.0085.
EExde IIB + H
2
:
T5 Ambient Temp. -55°C to +75°C.
T4 Ambient Temp. -55°C to +85°C.
This product is suitable to use in hazardous zones 1 and 2 with IIB + H
2
gas
group vapors present.
1.4.5.2 FM, CSA
The 40/40R Optical Flame Detector is certified to FM and CSA Explosion
Proof per:
Class I, Division 1, Groups B, C and D, T5 Ta = 85°C.
Dust Ignition Proof – Class II/III Division 1, Groups E, F and G.
Ingress Protection – IP67, IP66, NEMA 250 Type 6P.
For more details see Report Project ID3029553.
1.4.5.3 SIL-2 Approved (TÜV)
The 40/40R Optical Flame Detector is certified to SIL-2 requirement per IEC
61508.4, Chapter 3.5.12.
The alert condition according to SIL-2 can be implemented by:
Alert signal via 0-20mA current loop.
or
Alert signal via alarm relay and fault relay.
For more details and guidelines for configuring, installing, operating and
service – see SIL-2 Features on page 61 and TÜV Report No.
968/EZ348.00/009.
1.4.5.4 EN54-10
The 40/40R Optical Flame Detector is certified to EN54-10 and CPD.
The detector has been tested and approved per EN54-10 by LPCB
(BRE, UK).