Manual

SharpEye
TM
Single IR Flame Detector User Guide
32 Safety Precautions
3.2 Safety Precautions
After powering-up, the detector requires almost no attention in order to
function properly, but the following should be noted:
Follow the instructions in this guide and refer to the drawings and
specifications.
Do not expose the detector to radiation of any kind unless required for
testing purposes.
Do not open the detector housing, while power is applied.
Do not open the electronic compartment. This part should be kept closed
at all times and only opened in the factory. Opening the electronic
component side invalidates the warranty.
You should only access the wiring compartment to wire or remove the
detector or access RS485 terminals for maintenance.
Disconnect or disable external devices, such as automatic extinguishing
systems before carrying out any maintenance.
3.2.1 Default Functions Settings
Table 17 lists the default function configuration supplied with the detector.
Table 17: Default Function Values
Function Value Notes
Sensitivity 15
Alarm Delay A Antiflare
Alarm Latch No
Auxiliary Relay No
In wiring options 1, 2, 3, the Auxiliary
Relay is not available. This function is not
used.
Automatic BIT Yes
Alarm BIT No
Auxiliary BIT No
In wiring options 1, 2, 3, the Auxiliary
Relay is not available. This function is not
used.
EOL No
In wiring options 1, 2, 3, the Auxiliary
Relay is not available. This function is not
used.
Heat Mode Auto
Heat On
41°F
(5°C)
The detector starts heating the window
for any temperature below this value (in
degrees Celsius).
In order to change the default function use:
Mini Laptop Kit P/N 777820. Refer to manual TM777070 for
programming instructions when using the Mini Laptop Kit.