Manual

TM 40/40R, Rev (4) November 2010
Testing Procedures 33
USB RS485 Harness Kit P/N 794079-5. Refer to manual TM777050
for programming instructions when using the USB RS485 Harness
Kit.
HART protocol, refer to Manual 777030 for instructions.
3.3 Testing Procedures
This section describes the proof testing procedure for proper operation of
the detector. The detector can be tested using the Manual Built-in-Test or
the Spectrex Fire Simulator -20/20/312.
The detector performs internal test continuously and automatic BIT test
every 15 minutes for more details refer to Built-In-Test (BIT) on page 14.
This section includes the following topics:
Automatic BIT Test, page 33
Manual BIT Test. page 33
Testing with Fire Simulator Model 20/20-312, page 33
3.3.1 Automatic BIT Test
Check that the indicators show normal conditions. See Powering Up on
page 31.
3.3.2 Manual BIT Test
Important: If the function setup Alarm BIT and/or Auxiliary BIT are set
to Yes (default No), the Alarm, Auxiliary Relay and 0-20mA outputs are
activated during a Manual BIT. Therefore, automatic extinguishing systems
or any external devices that may be activated during BIT must be
disconnected.
To perform a Manual BIT:
1 Verify that the detector is Normal Mode.
2 Initiate Manual BIT. The results of successful and unsuccessful manual
BITs are detailed in Table 10 and Table 11.
3.3.3 Testing with Fire Simulator Model 20/20-312
The Fire Simulator Model 20/20-312 can be used to simulate exposure of
the detector to a real fire condition. The detector is exposed to radiation at
the required detection level. As a result, the detector will generate a Fire
Alarm signal. See Long Range Fire Simulator on page 55 for more
information.
Important: If the detector is exposed to a fire simulator, the Alarm and
Accessory Relays and 0-20mA are activated during the simulation.
Therefore, automatic extinguishing systems or any external devices, which
may be activated during this process, must be disconnected.