Manual

Technical Specifications 41
A Specifications
In this appendix…
Technical Specifications page 41
Electrical Specifications page 42
Outputs page 42
Mechanical Specifications page 45
Dimensions page 45
Weight page 45
Environmental Specifications page 45
A.1 Technical Specifications
Spectral Response
Single band IR 4.4-4.6 µm
Fuel ft. / m Fuel ft. / m
n-Heptane 50 / 15 Kerosene 37 / 11
Gasoline 50 / 15 Ethanol 95% 25 / 7.5
Diesel Fuel 37 / 11 Methanol 25 / 7.5
JP5 37 / 11 IPA (Isopropyl
Alcohol)
25 / 7.5
Methane* 16 / 5 Polypropylene
Pellets
10 / 3
LPG* 16 / 5 Office Paper 20 / 6
* 20" (0.5m) high, 8" (0.2m) width plume fire
Detection Range
(at highest Sensitivity
Setting for 1ft
2
(0.1m
2
) pan
fire)
Response Time Typically 5 seconds
Adjustable Time Delay Up to 30 seconds
Sensitivity Ranges 2 ranges for 1 ft
2
(0.1m
2
) n-heptane pan fire from 15 ft. (5m)
or 50 ft. (15m)
Fields of View
Horizontal 90°, Vertical 90°
Built-In-Test (BIT) Automatic (and Manual)