42 Outputs
A.2 Electrical Specifications
Table 20: Electrical Specifications
Operating
Voltage
Status All
Outputs
Without
0-20mA
Normal 1.61W 1.56W
Normal when Heater On 2.28W 2.16W
Alarm 2.64W 2.28W
Power
Consumption
(Max. 24VDC)
Alarm when Heater On 3.24W 2.88W
Normal 70mA 65mA
Normal when Heater On 95mA 90mA
Alarm 110mA 95mA
Maximum Current
(Max. 24VDC)
Alarm when Heater On 135mA 120mA
Normal 1.95W 1.85W
Normal when Heater On 2.56W 2.45W
Alarm 3.04W 2.56W
Power
Consumption
(Max. 18-32VDC)
Alarm when Heater On 3.68W 3.2W
Normal 90mA 85mA
Normal when Heater On 105mA 100mA
Alarm 130mA 115mA
Maximum Current
(18-32VDC)
Alarm when Heater On 160mA 145mA
Electrical Input Protection
The input circuit is protected against
voltage-reversed polarity, voltage transients,
surges and spikes according to MIL-STD-
1275B
A.3 Outputs
Electrical
Interface
There are five output-wiring options. These options must
be defined at the factory per the customer order and
cannot be changed at the customer facility.
See General Instructions for Electrical Wiring on page 47
for the wiring/terminal diagram for each option.
Unless otherwise specified, the default is Option 1. The
wiring arrangement is identified on the detector by the
part number (see Model and Types on page 2).
Option 1: Power, RS-485, 0-20mA (Sink), Fault I
Relay (N.C), Alarm Relay, (N.O) (see Figure 6).
Option 2: Power, RS-485, 0-20mA (Source) and
HART protocol, Fault Relay (N.O), Alarm Relay, (N.O),
(N.C).