56 Long Range Fire Simulator
D.1.1 Unpacking
Verify that you have received the following contents:
Delivery form
Fire Simulator with integral batteries
Battery charger
Storage case
D.1.2 Operating Instructions
Warning: Do not open the Fire Simulator to charge the batteries or for any
other reason in a hazardous area.
Caution: The following test simulates a real fire condition and may activate
the extinguishing system or other alarms. If this is not desired,
disconnect/inhibit them before the test and reconnect after the simulation.
To simulate a fire:
1 Aim the Fire Simulator towards the detector’s Target Point
Figure 15: 40/40R Detector Target Point
2
When testing keep a distance of at least 50 cm (20 inches) from the
detector.
3 Press the operation button once. Fire simulation lasts for 20 seconds.
The detector sends an alarm signal (solid red LED).
4 Wait 20 seconds before repeating the test.
5
Verify that the optical window is clean.
T