Note: Use the pull loop on the connector to disconnect modules. Do not
pull on the ribbon cable.
!
Attention
EXPLOSION HAZARD
In Class I, Division 2 applications, the bus connector must be
fully seated and the bus connector cover must be snapped in
place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on page 2-
4. If DIN rail mounting is used, an end stop must be installed
ahead of the controller and after the last 1762 I/O module.
Section 2.6
Field Wiring
Connections
Consider the following when wiring your system:
General
Power and output wiring must be in accordance with Class 1, Division 2 wiring
methods, Article 501-4(b) of the National Electric Code, NFPA 70, and in
accordance with the authority having jurisdiction.
The analog common (COM) is not connected to earth ground inside the module.
All terminals are electrically isolated from the system.
To ensure optimum accuracy for voltage type outputs, limit overall cable
impedance by keeping all analog cables as short as possible. Locate the I/O
system as close to your voltage type sensors or actuators as possible.
Digital and analog power must be supplied by an Isolated Secondary Limited
Energy Low Voltage source.
Use Belden™ 8761, or equivalent, shielded wire.