Owner manual

User’s Manual Pub. 0300246-01 Rev. B
Chapter 1
Module Overview
This chapter describes the 1762sc-OF8 output module. The module provides 8 analog
output channels that can be configured for current or voltage. Included is information
about:
General description
Output types and ranges
Data Formats
Hardware Features
System overview and module operation
Section 1.1
General
Description
The output module supports current and voltage type outputs. The module converts the
digital value stored in each channel’s output command word to an analog current or
voltage signal. Each output channel is individually configured via software for a specific
output type, data format, and provides open-circuit or short-circuit detection and
indication.
Section 1.2
Input Types
and Ranges
The tables below list the output types and their associated ranges.
Voltage Selection Range (V dc)
-10V to +10V - 11.0 to + 11.0
0 to +5V 0.0 to 5.5
0 to +10V 0.0 to +11.0
1 to +5V 0.0 to +5.5
Current Selection Range (mA)
0 to 20mA 0 to 20.4
4 to 20mA 3.92 to 20.4
Section 1.3
Data Formats
For each module the data can be configured for:
Engineering units
Scaled-for-PID
Raw/proportional data
Percent of full range