Owner manual

Micro800™ 4 Ch Universal Thermistor Input Module 14
Publication 0100198-01 Rev. A
The following table lists the memory location offset for each parameter
which is used when configuring the PLUGIN_READ, WRITE, and INFO
instructions.
Parameter Offset for Module Block (0x00 [0] to 0x1F [31])
Parameter
Offset
(Dec)
Comments
Default
MOD_ID_LO
0
Module ID
195
MOD_ID_HI
1
0
VENDOR_ID_LO
2
Vendor ID
58
VENDOR_ID_HI
3
0
PRODUCT_TYPE_LO
4
10
PRODUCT_TYPE_HI
5
0
PRODUCT_CODE_LO
6
80
PRODUCT_CODE_HI
7
0
MOD_REV_LO
8
Minor revision, 1-
255
1
MOD_REV_HI
9
Major revision, 1-
127
1
MOD_IRQ_STATUS
10
0: parity, 1: RA
only, 2: user-
defined, 3-7:
reserved
0
CONTROLLER_STATUS
11
Read-only, written
by controller
0
MOD_NUM_INPUT
12
Number of Input
channels
4
MOD_NUM_OUTPUT
13
Number of Output
channels
0
MOD_CONF_DATA_OFFSET
14
Starting address
of configuration
data
80
MOD_FEATURE
15
Module feature
register
32
MOD_STATUS
16
Module status
register
0
MODE_MODE_CONTROL
17
Module mode
control register
RESERVED
18 to 23
Returns value of
zero when read
MOD_INPUT_OFFSET
24
Starting address
offset of Input
Registers
32