Owner manual

Micro800™ 4 Ch Universal Thermistor Input Module 24
Publication 0100198-01 Rev. A
Environmental Specifications
Environmental
Tests
Industry Standards
Test Level Limits
Temperature
(Operating)
(Performance
Criteria A)
IEC60068-2-1: (Test Ad,
Operating Cold),
IEC60068-2-2: (Test Bd,
Operating Dry Heat),
IEC60068-2-14: (Test
Nb, Operating Thermal
Shock)
-20° C to 65° C (-4° F
to 149° F)
Temperature
(Non-operating)
(Performance
Criteria B)
IEC60068-2-1:
(Test Ab, Unpackaged
Non-operating Cold),
IEC60068-2-2:
(Test Bb, Unpackaged
Non-operating Dry
Heat),
IEC60068-2-14:
(Test Na, Unpackaged
Non-operating Thermal
Shock)
-40° C to 85°C (-40°
F to 185° F)
Operating Altitude
2000 meters (6561 feet)
Not tested
Humidity
(Operating)
(Performance
Criteria A)
IEC60068-2-30:
(Test Db, Unpackaged
Damp Heat):
5 to 95% non-
condensing
Vibration
(Operating)
(Performance
Criteria A)
IEC60068-2-6: (Test Fc,
Operating)
5 g @ 10 to 500 Hz,
0.030 in. max. peak-
to-peak
Shock (Operating)
(Performance
Criteria A)
IEC60068-2-27: (Test
Ea, Unpackaged Shock)
30 g,11 ms half-sine
(3 mutually
perpendicular axes)
Shock (Non-
operating)
(Performance
Criteria B)
IEC60068-2-27: (Test
Ea, Unpackaged Shock)
50 g, 11 ms half-sine
(3 mutually
perpendicular axes)
Radiated Emissions
CSIPR 11; Group 1,
Class A
FCC 47 CFR part 15
Class A
(Enclosure) Class A,
30 MHz 1 GHz