Owner manual

Micro800™ 4 Ch Universal Thermistor Input Module 27
Publication 0100198-01 Rev. A
Safety
Tests
Industry Standards
Test Level
Limits
UL Safety
UL 508 Industrial Control Equipment
Seventeenth Edition Dated January 28
1999, with revisions through July 11, 2005
(ANSI/UL 508-2005) (NRAQ, NRAQ7)
cUL CSA C22.2 No. 142 -M1987 Process
Control Equipment May 1987
UL Safety
UL
Hazardous
Locations
ULH ANSI/ISA12.12.012007
Nonincendive Electrical Equipment for Use
in Class I, Division 2 Hazardous (Classified)
Locations T4 or better
cULH CSA C22.2 No. 213-M1987 - Non-
incendive Electrical Equipment for use in
Class I Division 2 Hazardous Locations -
March 1987
UL Hazardous
Locations
CE Low
Voltage
Directive
IEC 61131-2 Programmable Controllers
Part 2: Equipment Requirements and Tests;
Second Edition 2003-02, Section 11-14
CE Low
Voltage
Directive
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C,
D or non-hazardous locations only. The following WARNING statement
applies to use in hazardous locations.
WARNING
EXPLOSION HAZARD
Substitution of components may impair
suitability for Class I, Division 2.
Do not replace components or disconnect
equipment unless power has been
switched off or the area is known to be
non-hazardous.
Do not disconnect equipment while the
circuit is live or unless the area is known
to be free of ignitable concentrations.
This product must be installed in an
enclosure which can only be opened with
the use of a tool.
All wiring must comply with N.E.C. article
501-4(b).