Owner manual

Micro800™ 4 Ch Universal Thermistor Input Module 9
Publication 0100198-01 Rev. A
Configuring the Module
The 2080sc-NTC is configured using 8 SINT configuration registers. The
following table describes the module configuration registers. The default
value of the configuration is represented by zeroes (0).
A configuration error will be set if any of the values marked <unused>
are passed.
(Configuration Assembly)
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Ch0
Config.
2x Bytes
Channel
Enable
Enable
Disable
0
1
Filter Frequency
17 Hz (default)
4 Hz
60 Hz
240 Hz
470 Hz
<unused>
0
0
0
0
1
1
0
0
1
1
0
x
0
1
0
1
0
x
Data Format
1
EU X1
EU X10
Raw/Proportional
<unused>
0
0
1
1
0
1
0
1
Linearization Equation
Resistance
0
0
Steinhart-Hart
0
1
Raw Proportional
1
0
<unused>
1
1
Unused
x
x
x
x
x
x
x
x
Ch1
Config.
2x Bytes
Data structure the same as channel 0 above
Ch2
Config.
2x Bytes
Data structure the same as channel 0 above
Ch3
Config.
2x Bytes
Data structure the same as channel 0 above
1
See Data Format