Instructions / Assembly

IN022 Rev M 0321 63 Saber Way, Ward Hill, MA 01835 | spruce.com
Mounting:Mountingbracketincluded.
Recommended ducting:RigidorFlexibleDucting.
Storage temperature range:32-100degreesF.
Normal operating temperature range:-20-120degreesF.
Maximum inlet air temperature:140degreesF.continuous.
Class B Insulation
Continuous Duty
3000 RPM
Thermally protected
Rated for Residential and Commercial use
Power Consumption @ 120 VAC, 60Hz (5.0 Amp Maximum)
Fan Model H h L D d Wt. lbs.
RL200 8.75" 7.38" 4.88" 9.50" 3.88" 6.5
RL300 9.38" 7.50" 5.88" 13.50" 5.88" 8.0
RL350 9.38" 7.50" 6.88" 13.50" 5.88" 8.0
RL450 10.50" 9.13" 6.88" 13.50" 7.88" 10.0
RL500 10.50" 9.13" 6.88" 13.50" 9.88" 10.0
RL600 N/A 10.00" 8.00" 15.88" 12.38" 12.0
RL SERIES PRODUCT SPECIFICATIONS
ThefollowingchartshowsfanperformancefortheRLSeriesCommercial/ResidentialFan:
Model
Typical CFM vs. Static Pressure
Max Static "WC
0" 0.2" 0.5" 0.75" 1.0" 1.25" 1.5"
RL200 163 150 123 101 76 54 28 1.78" WC
RL300 268 240 194 156 117 74 34 1.84" WC
RL350 300 280 238 201 164 127 89 2.11" WC
RL450 507 460 371 298 241 193 144 2.27" WC
RL500 545 500 419 349 275 222 170 2.35" WC
RL600 670 610 513 420 329 263 206 2.75" WC
Model Duct Watts L.2 Model Duct Watts L.2
RL200 4" 42-62 15 RL450 8" 92-152 55
RL300 6" 53-79 45 RL500 10" 97-153 140
RL350 6" 59-89 34 RL600 12" 150-215 240
L.2=EstimatedEquivalentLengthofRigidMetalDuctingresultingin.2inWCpressurelossforDuctSizelisted.LongerEquivalentLengthscan
beaccommodatedatFlowsLowerthanthatat.2inWCpressureloss(seeCFMVsStaticPressure“WCTable).Donotoperatefanabove80%of
maximumStaticPressureperperformancetable.