Submittal Sheet

3
5/98
© 1998 Square D All Rights Reserved
Definite purpose contactors are ideal for heating, air conditioning, refrigeration, data processing, and
food service equipment. New compact 1 and 2 pole contactors are available along with full size 2,
3, and 4-pole devices.
They feature quick connect terminals and binder head screws for easy wiring. Box lugs are standard on
40 ampere contactors and larger. An exclusive DIN track mounting option may reduce installation costs.
Coils can be changed on the Type DPA contactors quickly without a tool. Auxiliary contact modules
snap on either side of the Type DPA contactors.
Compact 1-Pole Contactors – 600 Vac Maximum
Full Load
Amperes
Locked Rotor Amperes
Resistive
Load Amperes
Horsepower Ratings
N.O.
Poles
Type
277 V 460 V 575 V 115 V 230 V
20 100 100 80 25 1 2 1 DP11
t
25 125 125 100 30 2 3 1 DP21
t
30 150 150 120 40 2 3 1 DP31
t
40 240 200 160 50
j
2 5 1 DP41
t
j50
A Res. limited to 277 V. All others rated 40 A Res. (above 277 V).
t
Voltage code must be specified to order this product. Refer to standard voltage codes listed below.
Compact 2-Pole Contactors – 600 Vac Maximum
c
Full Load
Amperes
Locked Rotor Amperes
Resistive
Load Amperes
Horsepower Ratings
N.O.
Poles
Type
277 V 460 V 575 V 115 V 230 V
20 100 100 80 30 1 2 2 DP12
t
25 125 125 100 35 2 3 2 DP22
t
30 150 150 120 40 2 5 2 DP32
t
40 240 200 160 50 2 5 2 DP42
t
c
Above 240 volts, all lines must be switched.
2, 3, and 4-Pole Contactors – 600 Vac Maximum
c
Full Load
Amperes
Locked Rotor Amperes Resistance
Load
Amperes
Horsepower Ratings
N.O.
Poles
Type
230 V 460 V 575 V 115 V 230 V 230 V 460/575 V
20 120 100 80 25 1 2 5 7
1
2
2
3
4
DPA12
t
DPA13
t
DPA14
t
25 150 125 100 35 2 3 7
1
2
10
2
3
4
DPA22
t
DPA23
t
DPA24
t
30 180 150 120 40 2 5 10 15
2
3
4
DPA32
t
DPA33
t
DPA34
t
40 240 200 160 50 3 7
1
2
10 20
2
3
4
DPA42
t
DPA43
t
DPA44
t
50 300 250 200 62 3 10 15 30
2
3
DPA52
t
DPA53
t
60 360 300 240 75 5 10 25 30
2
3
DPA62
t
DPA63
t
75 450 375 300 94 5 15 25 40
2
3
DPA72
t
DPA73
t
90 540 450 360 120 7
1
2
20 30 50
2
3
DPA92
t
DPA93
t
120 720 600 480 120 7
1
2
20 30 50
2
3
DPA122
t
DPA123
t
132 800 800 520 132 .... .... .... .... 3 SYD138
t
220 1500 1500 1200 220 .... .... .... .... 3 SYD230
t
352 2200 2200 1800 352 .... .... .... .... 3 SYD368
t
c
Above 240 volts, all lines must be switched.
Coil Voltage Codes
Voltage
Code Type DP, DPA Code Type DPA122, DPA123, SYD
60 Hz 50 Hz
24
24
120
208
208-240
230-240
277
480
600
24
...
110
...
220
220
...
440
550
V14
...
V02
...
V09
...
V04
V06
V07
f
V12
q
V01
p
V02
V08
...
V03
V04
V06
V07
q
24 V 50 Hz only.
p
Available on Types DPA122, DPA123, and SYD138 only.
f
Not available for Type DP one- and two-pole devices.
Definite Purpose Contactors
Types DP, DPA and SYD — Class 8910
Compact Design
Industry Standard
Mounting
Double Break
Contacts
Low Coil VA
Straight-Through
Wiring
Low Cost
Type DPA33V02
3-Pole
Type DP31V02
1-Pole
Type DP32V02
2-Pole

Summary of content (2 pages)