Energy Guide

© 2019 Schneider Electric
All Rights Reserved
3-11
www.se.com/us
UL Listed Maximum Short Circuit Current
Ratings—AC only
Heavy Duty Safety Switches
Class 3110 / Refer to Catalog 3100CT1602
UL Listed Maximum Short Circuit Current Ratings—AC only
NOTE: Consult the wiring diagram of the switch
to verify the UL Listed short circuit current rating.
Table 3.16: Fusible Safety Switches
Heavy Duty
Safety Switch Type
UL Listed
Fuse Class
UL Listed Short Circuit
Current Ratings
Fusible
H, K
10 kA
R, J, L
200 kA [31]
Non-Fusible Safety Switches
Systems equal or less than 10 kAIR SCCR —Any brand of circuit breaker or fuse not
exceeding the ampere rating of the switch may be used in conjunction with a non-
fusible safety switch.
Systems above 10 kAIR SCCR—The UL Listed short circuit current rating for Square
D non-fusible switches is based upon the switch being used in conjunction with fuses
or Square D circuit breakers or Mag-Gard motor circuit protectors.
Table 3.17: Non-Fusible Safety Switches
[32] [33]
Switch Rating
(A)
Fuse or Circuit Breaker Type [34]
3-Phase
250 Vdc /
600 Vdc
240 Vac 480 Vac 600 Vac
With Upstream Fuse Protection
All
H, K
10 kA 10 kA 10 kA
Up to 10
kA
R,T,J,L
200 kA 200 kA 200 kA
With Upstream Circuit Breaker Protection
All
Any brand circuit breaker
10 kA 10 kA 10 kA
30–100 HD 25 kA 18 kA 14 kA
Up to 10
kA
30–100 HG 65 kA 35 kA 18 kA
30–100 HJ 65 kA 35 kA 25 kA
30–100 HL 65 kA 35 kA 35 kA
30–100 HR 65 kA 35 kA 35 kA
30–100 FA 14 kA 14 kA 14 kA
30–100 FH 18 kA 18 kA 18 kA
200
HD, JD
25 kA 18 kA 14 kA
200
HG, JG
65 kA 35 kA 18 kA
200
HJ, JJ
65 kA 35 kA 25 kA
200
HL, JL
65 kA 35 kA 35 kA
200
HR, JR
65 kA 35 kA 35 kA
400 LA 22 kA 22 kA 22 kA
400 LH 25 kA 25 kA 25 kA
400–600 LD 25 kA 18 kA 14 kA
400–600 LG 65 kA 35 kA 18 kA
400–600 LJ 100 kA 65 kA 25 kA
400–600 LL 100 kA 65 kA 50 kA
400–600 LR 100 kA 65 kA 65 kA
3
SAFETY SWITCHES
[31] On 600 V, 200 A switches, 100,000 A max. on corner grounded delta when protected by Class J or R fuses.
[32] For NEMA Type 4X Fiberglass Reinforced Polyester switches, see page 3-12.
[33] NEMA Type 7/9 SCCR 10 kAIR 600 Vac maximum.
[34] Ampere rating of fuse or circuit breaker not to exceed switch ampere rating.
9/13/2019