Heavy Duty Safety Switches Special Applications
www.se.com/us
Class 3110 / Refer to Catalog 3100CT1602
Special Application Heavy Duty Safety Switches
316 Grade Stainless Steel—NEMA Type 3, 3R, 4, 4X, 5, 12
H361SS
316 stainless steel enclosure safety switches offer superior corrosion resistance to a
wider range of chemicals than 304 stainless switches. 316 better resists chloride and is
often used in marine, waste treatment and transportation applications. Use watertight
hubs, see Hubs, page 3-15. Equipment grounding lugs are supplied as standard through
200 A. See Table 3.42 Terminal Lug Data, page 3-21 for wire Termination data for
grounding lugs. (For 304 stainless switches, see 240 Volt, page 3-8 and 600 Volt, page
3-9.
Table 3.18: 316 Grade Stainless Steel 3 Pole 600 Vac, 600 Vdc
Amperes
Cat. No
Horsepower Ratings–
480 Vac[35] 600 Vac [35] 600 Vdc [36]
Std. Max. Std. Max. Max.
Fusible—3P, 600 Vac, 600 Vdc
 30
 60
100
200
400
600
H361SS
H362SS
H363SS
H364SS
H365SS
H366SS
 5
15
25
50
100
150
 15
 30
 60
125
250
400
7-1/2
15
30
60
125
200
 20
 50
 75
150
350
500
15
30
50
50
50
50
Non-Fusible—3P, 600 Vac, 600 Vdc
 30
 60
100
200
400
600
HU361SS
HU362SS
HU363SS
HU364SS
HU365SS
HU366SS
 20
 50
 75
125
250
400
 30
 60
100
150
350
500
15
30
50
50
50
50
Fiberglass Reinforced Polyester Enclosures—NEMA Type 4X
H363DF
Fiberglass reinforced polyester enclosures are watertight, corrosion resistant, and
impervious to windblown dust, rain, and splashing liquid. The molded fiberglass is
extremely stable in a wide range of operating temperatures and can withstand heavy
impact. Switches are furnished with hubs, conduit provisions Table 3.43, and equipment
grounding lugs. See CAD drawings of the switch to verify the UL listed short circuit
current rating or the enclosed safety switch catalog. UL Listed.
Table 3.19: Fiberglass Reinforced Polyester Enclosures NEMA Type 4X 3 Pole 600 Vac, 600 Vdc
Amperes
Cat. No.
Solid Neutral
Assembly Kit
Class R
Fuse Kits
Electrical Interlock Kits
Field-Installed Cat. No.
Horsepower Ratings–
Hubs[37]
480 Vac [38] 600 Vac [38] 600 Vdc [39]
Cat. No.
1 NO/1 NC
Contacts
2 NO/2 NC
Contacts
Std. Max. Std. Max. Max.
Fusible—3P, 600 Vac, 600 Vdc
 30 H361DF SN03 RFK06 9999TC10 9999TC20  5  15 7-1/2  20 15 3/4
 60 H362DF SN03 RFK06H 9999TC10 9999TC20 15  30 15  50 30 1-1/4
100 H363DF SN0610 RFK10 9999TC10 9999TC20 25  60 30  75 50 2
200 H364DF HRK1020 9999R8 9999R9 50 125 60 150 50 2-1/2
Non-Fusible—3P, 600 Vac, 600 Vdc
 30 HU361DF SN03 9999TC10 9999TC20  20  30 15 3/4
 60 HU362DF SN03 9999TC10 9999TC20  50  60 30 1-1/4
100 HU363DF SN0610 9999TC10 9999TC20  75 75 50 2
200 HU364DF 9999R8 9999R9 125 150 50 2-1/2
3
SAFETY SWITCHES
[35] Std.—Using fast acting, one time fuses. Max.—Using dual element time delay fuses.
[36] For switching dc use two switching poles.
[37] Two hubs and hub drilling template are provided for field installation.
[38] Std.—Using fast acting, one time fuses. Max.—Using dual element time delay fuses.
[39] For switching dc use two switching poles.