Energy Guide

3-6
© 2019 Schneider Electric
All Rights Reserved
General Duty Safety Switches
Accessories and Lug Data
www.se.com/us
Class 3130 / Refer to Catalog 3100CT1602
Field-Installed Fuse Puller Kits
Fuse Puller Kit
Series F Fusible Switches Only
Kit consists of three fuse pullers as required for a 3P, fusible, 60 or 100 A general duty
switch. Kits can be installed only in 60 or 100 A Series F fusible switches.
Table 3.6: Fuse Puller Kits
Switch Ampere Rating
Series No. Cat. No.
60 F FPK03
100 F FPK0610
Field-Installed Electrical Interlock Kits
Electrical interlocks for Series F 100–200 A general duty safety switches & Series F 60 A fusible general duty safety switches are available in kit
form for field installation. Each kit contains instructions for proper field mounting. A pivot arm operates from switch mechanism, breaking the
control circuit before the main switch blades break. Switches with electrical interlocks installed are UL Listed.
Table 3.7: Electrical Interlock Kit
Switch
Amperes Rating
Electrical Interlock Kit Cat. No.
[21]
Fusible Series F 60 EIK031 or EIK032
Series F 100–200 EIK1 or EIK2
Table 3.8: Electrical Interlock Contact Ratings [22]
Interlock Type
AC 50 or 60Hz DC
Volts Make Break Cont. Volts
Make /
Break
Cont.
1 N. O. / 1 N. C.
Contact
(-1 Suffix [23])
120 40.00 A 15.00 A 15.00 A 115 0.50 A 15.00 A
240 20.00 A 10.00 A 15.00 A 230 0.25 A 15.00 A
2 N. O. / 2 N. C.
Contacts
(-2 Suffix [24])
120 30.00 A 3.00 A 10.00 A 115 1.00 A 10.00 A
240 15.00 A 1.5 A 10.00 A 230 0.30 A 10.00 A
Equipment Grounding Kits
PK3GTA1
GTK0610 PK0TGA2
Table 3.9: Equipment Grounding Kits
Switch Ampere Rating
Cat. No.
Lug Wire Range (AWG)
30 [25]
Std.
(1) 14 10 Cu or
(1) 12 8 Al
30 PK3GTA1
(3) 14 4 Cu or (3) 12 4 Al or
(6) 14 12 Cu or (6) 12 10 Al
60 [26]
GTK03
(2) 14 4 Cu or (2) 12 4 Al
(4) 14 12 Cu or (4) 12 10 Al
100 GTK0610
(2) 14 1/0 Cu or (2) 12 1/0 Al
(2) 14 6 Cu or (2) 12 6 Al
200 PKOGTA2
(2) 10 2/0 Cu or (2) 6 2/0 Cu Al
400, 600
PKOGTA2 [27] (2) 10 2/0 Cu or (2) 6 2/0 Cu Al
800 PKOGTA3
(6) 6 3/0 Al/Cu Max.
Field-Installed Lug Kit 400 A 600 A
Table 3.10: Field-Installed Lug Kit 400 A 600 A
Switch Ampere Rating Lug Kit Cat. No. Wire Range/NEC Lug Wire Range
400 or 600 Series [28]
GD4060LK
1-1/0-600 kcmil
2-1/0-500 kcmil
4-1/0-250 kcmil
2-1/0-600 kcmil
4-1/0-250 kcmil
Terminal Lug Data
Table 3.11: Terminal Lug Data [29]
Amperes
Conductors
Per Phase
Wire Range
Wire Bending Space Per NEC Table 312.6
AWG/kcmil
Lug Wire Range
AWG/kcmil
 30 [30]
1
12–8 (Al) or 14–8 (Cu) 12–8 (Al) or 14–8 (Cu)
 30 1
12–6 (Al) or 14–6 (Cu) 12–6 (Al) or 14–6 (Cu)
 60 1
12–3 (Al) or 14–3 (Cu) 12–2 (Al) or 14–2 (Cu)
100 1
12–1 (Al) or 14–1 (Cu) 12–1/0 (Al) or 14–1/0 (Cu)
200 1
6 –250 (Al/Cu) 6 –300 (Al/Cu)
400
NEMA
Type 1
1 or
2
1/0 –600 (Al/Cu) or
1/0 –300 (Al/Cu)
(1) 1/0 –750 (Al/Cu) or
(2) 1/0 –300 (Al/Cu)
400
NEMA
Type 3R
2
1/0–250 (Al/Cu)
(1) 1 –600 (Al/Cu) or
(2) 1/0 –250 (Al/Cu)
600 2
4 –500 (Al/Cu) 4 –600 (Al/Cu)
800 3
3/0 –500 (Al/Cu) 3/0 –500 (Al/Cu)
3
SAFETY SWITCHES
[21] Electrical interlock kit catalog numbers with -1 suffix indicate one normally open and one normally closed contact; -2 indicates two normally open and two normally closed contacts. Kits are
UL Listed.
[22] Single-pole single-throw interlock kits are rated 1/2 hp at 110 and 220 Vac.
[23] -1 Suffix uses a 9007A01 limit switch.
[24] -2 Suffix uses a 9007C03 limit switch.
[25] Light duty safety switches.
[26] 60 A non-fusible switches accept PK3GTA1.
[27] Two required if ground conductors are run in parrellel.
[28] Not suitable for use on 400 A NEMA Type 3R.
[29] 30–100 A switches suitable for 60
o
C or 75
o
C conductors. 200–800 A switches suitable for 75
o
C conductors.
[30] Light duty switches only.
9/13/2019