Energy Guide

© 2019 Schneider Electric
All Rights Reserved
3-9
www.se.com/us
600 Volt—Single Throw Fusible Switches Heavy Duty Safety Switches
Class 3130 / Refer to Catalog 3100CT1602
600 Volt—Single Throw Fusible
Table 3.14: 600 Volt—Single Throw Fusible
System Amperes
NEMA
Type 1
Indoor
NEMA Type
3R
Rainproof
(Bolt-on
Hubs [10])
NEMA Type
4, 4X, 5 [11]
304 Stainless Steel
(316 stainless [12])
Dust tight,
Watertight,
Corrosion
Resistant
(Watertight Hubs
[10])
NEMA Type
12K
With
Knockouts
(Watertight
Hubs [10])
NEMA Type
3R, 5 or 12 [13]
Without
Knockouts
(Watertight Hubs
[10])
Horsepower Ratings
480 Vac 600 Vac
dc [14]
Std.
(Using
Fast
Acting,
One Time
Fuses)
Max.
(Using
Dual
Element,
Time
Delay
Fuses)
Std.
(Using
Fast
Acting,
One
Time
Fuses)
Max.
(Using
Dual
Element,
Time
Delay
Fuses)
Cat. No. Cat. No. Cat. No. Cat. No. Cat. No.
250 600
2-Wire (2 Blades and Fuseholders)—600 Vac, 600 Vdc
  30
Use three-wire devices
for two-wire applications
  60
 100
 200
 400 H265 H265R H265DS H265AWK
100 [15] 250 [15]
50 50
 600 H266 H266R H266DS H266AWK
150 [15] 400 [15]
50 50
 800 H267
H267R [16]
H267AWK 50
1200 H268
H268R [16]
H268AWK 50
3-Wire (3 Blades and Fuseholders)—600 Vac, 600 Vdc
  30 H361 H361RB H361DS H361A H361AWK   5  15   7-1/2  20  5 15
  30
H3612 [17] H3612RB [17]
H3612A [17] H3612AWK [17]
  5  15   7-1/2  20 15
  60 H362 H362RB H362DS H362A H362AWK  15  30  15  50 30
 100 H363 H363RB H363DS H363A H363AWK  25  60  30 100 50
 200 H364 H364RB H364DS H364A H364AWK  50 125  60 150 40 50
 400 H365 H365R H365DS H365AWK 100 250 125 350 50 50
 600 H366 H366R H366DS H366AWK 150 400 200 500 50 50
 800 H367
H367R [16]
H367AWK 200 500 250 500 50
1200 H368
H368R [16]
H368AWK 200 500 250 500 50
4-Wire (3 Blades and Fuseholders, 1 Neutral)—600 Vac, 600 Vdc
  30 H361N H361NRB
Use three-wire devices,
See Field-Installed Neutral Assemblies, page 3-17
  5  15   7-1/2  20 15
  60 H362N H362NRB  15  30  15  50 30
 100 H363N H363NRB  25  60  30  75 50
 200 H364N H364NRB H364NDS H364NA H364NAWK  50 125  60 150 40 50
 400 H365N H365NR H365NDS H365NAWK 100 250 125 350 50 50
 600 H366N H366NR H366NDS H366NAWK 150 400 200 500 50 50
 800 H367N
H367NR [16]
H367NAWK 200 500 250 500 50
1200 H368N
H368NR [16]
H368NAWK 200 500 250 500 50
4-Wire (4 Blades and Fuseholders)—600 Vac, 600 Vdc [18]
 30 H461 H461DS H461AWK   7-1/2  20  10  25  5 15
 60 H462 H462DS H462AWK  15  40  20  50 10 30
100 H463 H463DS H463AWK  25  60  30  75 20 30
200 H464 H464DS H464AWK  50 125  60 150 40 50
400 H465 H465AWK 100 250 125 350 50 50
600 H466 150 400 200 500 50 50
6-Wire (6 Blades and Fuseholders)—600 Vac[18]
100 H663DS H663AWK  25  60  30  75
200 H664DS H664AWK
For applications requiring motor disconnect capability, see Electrical
Interlock Kits, page 3-16
Accessories: see page 3-15
Dimensions: NEMA Type 1 and 3R, see page 3-22
Dimensions: NEMA Type 4, 4X and 5 Stainless and NEMA Type 12, see page 3-23
Class H, R, J, and L Fuse Provisions:
Class R Fuse
Class H or K Fuse Provisions: Fusible Square D 30–600 A heavy duty safety switches accept Class H or K fuses as
standard. With Class H or K fuses installed, the switch is UL Listed for use on systems with up to 10 kA available fault
current.
Class R Fuse Provisions: Fusible Square D 30–600 A heavy duty safety switches will accept Class R fuses as
standard. A field-installed rejection kit is available which, when installed, rejects all but Class R fuses. With the installation
of the rejection kit and Class R fuses, the switch is UL Listed for use on systems with up to 200 kA available fault current.
See Class R Fuse Kits, page 3-16.
Class J Fuse Provisions: Provisions for installing Class J fuses are included in 30–400 A 600 Volt, and 100–400 A 240
Volt, fusible heavy duty safety switches. Conversion to Class J fuse spacing requires relocating the load side fuse base
assembly from the standard Class H fuse location to an alternate position as marked in the enclosure. With Class J fuses
installed, the switch is UL Listed for use on systems with up to 200 kA available fault current. Switches rated 600 A, 240
or 600 Volt, require the addition of an adapter kit, H600J. One kit per three-pole switch.
Class L Fuse Provisions: Fusible 800 A and 1200 A safety switches use Class L bolt-in fuses and are rated for use on
systems with up to 200 kA at 600 Vac maximum. 1200 A switches accept class L fuses from 601–1200 A, 800 A switches
accept class L fuses from 601–800 A.
3
SAFETY SWITCHES
[10] For Rainproof Bolt-On Hubs and Watertight Hubs see Hubs, page 3-15.
[11] Complete rating is NEMA Type 3, 3R, 4, 4X, 5 and 12..
[12] See Table 3.18 316 Grade Stainless Steel 3 Pole 600 Vac, 600 Vdc, page 3-12.
[13] Also suitable for NEMA Type 3R application by removing drain screw from bottom endwall.
[14] For switching dc, use two outside switching poles.
[15] For corner grounded delta systems, use switching poles for ungrounded conductors. See data bulletin 2700DB0202 for additional information.
[16] Suitable for NEMA Type 5 applications with drain screw installed.
[17] 60 A switch with 30 A fuse spacing and clips. Must use 60 A enclosure accessories including electrical interlocks.
[18] Not suitable for use as service equipment.
9/13/2019