How to Guide

Commercial Pressure and Float Switches for Power Circuits
Selection Guide—Pumptrol™ Commercial Pressure Switches
5
03/2011
© 2011 Schneider Electric
All Rights Reserved
Pumptrol Family 9013FRG 9013FHG 9013G
Applications
Type of Installation Power circuit Power circuit Power circuit
Controls Fresh or sea water Air only Water or air
Type of Operation
Reverse acting, contacts open on
falling pressure (adjustable
differential)
Control of electrically driven air
compressors, contacts open on rising
pressure (fixed differential, adjustable
cut-out), diaphragm actuated
Light industrial, with higher electrical
ratings for direct control of motors in
pumps and compressors, contacts
open on rising pressure (adjustable
differential)
Size / Range
psi 8–150 40–200 10–250
bar 0.41–10.34 2.76–13.79 0.69–17.24
Conforming to Standards NEMA A300 UL508 NEMA A600 UL508 NEMA A600 UL508
Product Certifications
UL File: E12158 CCN NKPZ
CSA File: LR 25490
Class 3211 06
UL File: E12158 CCN NKPZ
with Form T
CSA File: LR 25490
Class 3211 06
UL File: E12158 CCN NKPZ
(except GHR and GSR)
UL File: E12443 CCN NOWT
(for GHR and GSR)
CSA File: LR 25490 Class 3211 06
(except GHR and GSR)
CSA File: LR 26817 Class 3218 05
(for GHR and GSR)
Dimensions (l x h x w) in inches (mm)
3.76 x 2.8 x 2.78
(95.5 x 71.12 x 70.6)
3.76 x 2.8 x 2.78
(95.5 x 71.12 x 70.6)
3.68 x 3.85 x 3.44
(93.47 x 97.79 x 87.37)
Contact Blocks (snap action contacts) 2 N.O. 2 N.C. 2 N.C.
Degree of Protection
NEMA Type 1, NEMA Type 3R,
and IP20
NEMA Type 1, NEMA Type 3R,
and IP20
NEMA Type 1, NEMA Type 3R, NEMA
Type 7, NEMA Type 9, and IP20
Connections
Electrical Screw terminals Screw terminals Screw terminals
Fluid Multiple Multiple Multiple
Cable Entries 2 2 3 knock-outs available
Catalog Numbers 9013FRG••• 9013FHG••• 9013G•••
Specifications Page 20 Page 20 Page 20
Interpretation of Catalog Numbers Page 21 Page 21 Page 21
Other versions:
Form B7, one grommet, CE
Form B8, two grommets, CE
NOTE: Inclusion of B7 or B8 grommets will
negate UL/CSA approvals for the device, but
they may be used for applications which do
not require UL/CSA approvals.