Use and Care Manual

Preventive Maintenance and Troubleshooting Guidelines for Class 9013F and 9013G Pressure Switches 9013DB0701
Troubleshooting 12/2007
© 2007 Schneider Electric All Rights Reserved6
Switch operates
mechanically,
but not
electrically
No power to switch
Apply power to the switch.
Check the circuit breaker and/or disconnect switch. If the breaker is
tripped on a new installation, check the switch wiring. Reset the breaker
(disconnect).
Apply power to the switch.
Confirm the wiring of the switch.
Damaged or improperly
installed wiring
Wired to the wrong contact.
Complete Steps 1–5 of “Providing Routine Maintenance” on page 1.
Wire to the correct contacts.
Corroded or loose connections
Make new connections or tighten the
existing connections.
Damaged switch contacts
Replace the switch contacts or entire
switch.
Contacts overloaded (welded)
Complete Steps 6–10 of “Providing Routine Maintenance” on page 1.
Remove the pressure switch from
the pipe and confirm that the entry
to the diaphragm is free of silt and
obstructions.
Confirm that any check valves in the
system between the source and the
pressure tank are functioning
properly.
Confirm that pressure reading at the
pressure switch accurately reflects
the pressure in the pressure tank.
Low pressure cut-out (M4) has cut-
out.
Repair or replace the switch if
defective.
Clean plumbing and pressure port
(replace if defective).
Table 2: Troubleshooting Tips (continued)
Condition Possible Causes Description/Corrective Action
Corrective Procedure for
Qualified Service Personnel