Instruction Manual Commercial gas water heaters 500 Tennessee Waltz Parkway Ashland City, TN 37015 MODELS SBL95 199NE SBL85 275NE(A) SBL85 390NE(A) Ultra Low NOx SERIES 100 INSTALLATION - OPERATION - SERVICE - MAINTENANCE - LIMITED WARRANTY Complies with SCAQMD Low NOx Rule 1146.2 WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
Table Of Contents Safe Installation, Use and Service............................. 3 Outdoor Air Through One Opening..................................... 16 APPROVALS.............................................................................. 3 Outdoor Air Through Two Horizontal Ducts......................... 16 General Safety Information.......................................... 4 Outdoor Air Through Two Vertical Ducts............................. 17 Precautions......................................
Safe Installation, Use and Service The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual.
General Safety Information Fire or Explosion Hazard Fire Hazard Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. For continued protection against risk of fire: Avoid all ignition sources if you smell gas. Do not expose water heater controls to excessive gas pressure. Do not install water heater on carpeted floor. Do not operate water heater if flood damaged. Use only the gas shown on the water heater rating label.
General Safety Information Read and understand this instruction manual and the safety messages herein before installing, operating or servicing this water heater. Explosion Hazard Overheated water can cause water tank explosion. Failure to follow these instructions and safety messages could result in death or serious injury. Properly sized temperature and pressure relief valve must be installed in the opening provided. This manual must remain with the water heater.
Introduction Thank You for purchasing this water heater. Properly installed and maintained, it should give you years of trouble free service. below) in the field involved. Installation skills such as plumbing, air supply, venting, gas supply and electrical supply are required in addition to electrical testing skills when performing service. Abbreviations Used ANSI Z223.1 2012 Sec. 3.3.
Features and Components Controls 130 RESET BUTTON 140 CONTROL BOX ON/OFF SWITCH VARIABLE FREQUENCY DRIVE LED LIGHTS DIGITAL THERMOSTAT DIGITAL THERMOSTAT Figure 3. I/O MODULE LOW SPEED I/O MODULE HIGH SPEED BLOCKED INLET SWITCH Electronic Ignition Control Each heater is equipped with an ignition control. The solid state ignition control (Figure 4), ignites the burner by utilizing a spark igniter.
Installation considerations Rough In Dimensions I TOP OUTLET 1 1/2" NPT F TOP INLET 1 1/2" NPT K 1 1/2" NPT A C M DH L G E TOP VIEW B J BACK VIEW FRONT VIEW Figure 6. Table 1. Rough-In-Dimensions SBL95 199NE inches cm 76 193.0 29.8 11 3/4 78 1/4 198.8 65 3/4 167.0 25 3/4 65.4 21 53.3 3/4 NPT 66 1/4 168.3 6 15.2 27 3/4 70.5 1 1/2 NPT 1 1/2 NPT 41 104 790 lbs. 358 Kg. - Model Dim. A B C D E F G H I J K L M Approx. Shipping Weight STD Approx.
the water heater must be placed on a metal or wood panel extending beyond the full width and depth by at least 3 inches in any direction. If the heater is installed in a carpeted alcove, the entire floor shall be covered by the panel. Also, see the DRAINING requirements in MAINTENANCE Section. Locating the Water Heater CAUTION Property Damage Hazard THE HEATER SHALL BE LOCATED OR PROTECTED SO IT IS NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE. • All water heaters eventually leak.
Insulation Blanket Breathing Hazard - Carbon Monoxide Gas Do not obstruct water heater air intake with insulating blanket. Gas and carbon monoxide detectors are available. Install water heater in accordance with the instruction manual. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products.
RAM ULATION Some circulating pumps are manufactured with sealed bearings and do not require further lubrication. Some circulating pumps must be periodically oiled. Refer to the pump manufacturer’s instructions for lubrication requirements. High Altitude Installations CIRCULATING PUMP WIRING DIAGRAM Fire and Explosion DISHWASHER LOOP WITH TOGGLE SWITCH CIRCULATING PUMP WIRING DIAGRAM STORAGE TANK OR BUILDING RECIRCULATION NOTE: USE SEPARATE 120 VAC POWER SUPPLY FOR PUMP CIRCUIT.
Installation Requirements 4. Gas Supply Systems Low pressure building gas supply systems are defined as those systems that cannot under any circumstances exceed 14” W.C. (3.49 kPa) (1/2 PSI Gauge). These systems do not require pressure regulation. Measurements should be taken to insure that gas pressures are stable and fall within the requirements stated on the water heater rating plate.
expansion. Contact a local plumbing service agency to have a thermal expansion tank installed. HOT WATER OUTLET See Water Line Connections on page 20 and Water Piping Diagrams on page 34. 12” TO 15” (30-38 cm) Temperature-Pressure Relief Valve TEMPERED WATER OUTLET CHECK VALVE COLD WATER INLET CHECK VALVE Explosion Hazard MIXING VALVE Temperature-Pressure Relief Valve must comply with ANSI Z21.22CSA 4.4 and ASME code.
No valve or other obstruction is to be placed between the Temperature-Pressure Relief Valve and the tank. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.
provide combustion, ventilation and dilution air. Air Requirements Unusually Tight Construction In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Confined Space section that follows.
Multiple Heater Manifold Outdoor Air Through One Opening Figure 13 and tables on pages 18 and 19 should be used for horizontally manifolding two or more heaters. Figure 15. Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. See Figure 14. The water heater shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (l50 mm) from the front of the appliance.
When ducts are used, they shall be of the same cross sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than 3 inches. Outdoor Air Through Two Vertical Ducts The illustrations shown in this section of the manual are a reference for the openings that provide fresh air into confined spaces only. Air From Other Indoor Spaces Do not refer to these illustrations for the purpose of vent installation.
Table 6. TECHNICAL DATA VENTING TYPE B GAS VENT Multiple Gas Fired Tank-Type Heaters When venting multiple tank type heaters using Type B vent pipe, follow the installation diagram (figure 13) and tables below which give sizing and data based upon NFPA 54/ANSI Z223. 2006. MODEL SBL95 199NE Input: 199,000 Btu/hr Total Vent Height (Feet) Vent Connector Size: 6 inches 6 8 10 15 20 30 50 100 Input Btuh/hr Rise 199,000 1 Ft. 7 7 199,000 2 Ft. 7 7 6 6 6 3 Ft.
Table 7. TECHNICAL DATA VENTING (Continued) MODEL SBL85 275NE(A) Input: 275,000 Btu/hr Total Vent Height (Feet) Vent Connector Size: 6 inches 6 8 10 15 20 30 50 100 Input Btu/hr Rise 275,000 1 Ft. 8 8 7 7 6 6 6 6 275,000 2 Ft. 8 8 7 7 6 6 6 6 3 Ft.
Water heater installation Water Line Connections T&P Valve Discharge Pipe The water piping installation must conform to these instructions and to all local code authority having jurisdiction. Good practice requires that all heavy piping be supported. Read and observe all requirements in the following sections before installation of the water piping begins: 1. Water Temperature Control and Mixing Valves on page 12. 2. Dishwashing Machines on page 13. 3. Temperature-Pressure Relief Valve on page 13.
TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE CONTROL AND MIXING VALVES ON PAGE 12. IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES. Installation Diagrams - Top Inlet/Outlet Usage Use of the top inlet water connection requires an inlet dip tube (refer to figure 19). The tube is supplied in the heater. Follow caution labels if applying heat to this fitting.
Heater Wiring All electrical work must be installed in accordance with the latest version of the National Electrical Code ANSI/NFPA No. 70 and must conform to all local code authority having jurisdiction. AN ELECTRICAL GROUND IS REQUIRED TO REDUCE RISK OF ELECTRICAL SHOCK OR POSSIBLE ELECTROCUTION. The controls of this water heater are polarity sensitive. Be certain to properly wire the hot and neutral connections.
Supply Gas Regulator Gas Piping The minimum gas supply pressure must not be less than 3.5" w.c. (0.87 kPa). Contact your local gas service company to ensure that adequate gas service is available and to review applicable installation codes for your area. Do not subject the gas valve to inlet gas pressures of more than 14.0” W.C. (3.48 kPa). A supply gas regulator is necessary if higher gas pressures are encountered. See Gas Pressure Requirements and Supply Gas Regulator sections on page 12.
Start up Prior to Start Up Initial Start Up Installation and start up of this water heater requires abilities and skills equivalent to that of a licensed tradesman in the field involved, see Qualifications on page 6. Required Test Equipment U-tube manometer, pressure gauge, or digital manometer. Recommended range: 20” W.C. (5 kPa). Note: All test equipment must be acclimated to ambient temperature before calibration and use. Preparation 1. Adjust the thermostat to the lowest temperature setting. 2.
Supply gas pressure shall be measured while the water heater is not firing (static pressure) and while the water heater is firing at full capacity (dynamic pressure). 7. If improper venting is observed during any of the above tests, the venting system must be corrected. FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS.
Sequence of Operation The following information will describe the Sequence of Operation for this water heater. 8. If the Flame Sensor does not detect a strong enough flame, the Ignition Control shuts off the Gas Valve and allows the Blower to purge the unit for 30 seconds. At that time, the Ignition Control restarts with step 6. It will try and ignite the main burners 2 more times. If the unit does not light, the Ignition Control will wait 15 minutes and then restart at step 6.
Sequence of Operation Flow Chart Description of this flow chart can be found in the “SEQUENCE OF OPERATION” section found on page 26.
Maintenance Expansion on page 13. The Temperature-Pressure Relief Valve is not intended for the constant relief of thermal expansion. Temperature-Pressure Relief Valve leakage due to pressure build up in a closed system that does not have a thermal expansion tank installed is not covered under the limited warranty. Thermal expansion tanks must be installed on all closed water systems. DO NOT PLUG THE TEMPERATURE-PRESSURE RELIEF VALVE OPENING. THIS CAN CAUSE PROPERTY DAMAGE, SERIOUS INJURY OR DEATH.
Draining and Flushing Periodic Removal of Lime Deposits from Tank Type Commercial Water Heaters The amount of calcium carbonate (lime) released from water is in direct proportion to water temperature and usage, see chart. The higher the water temperature or water usage, the more lime deposits are dropped out of the water. This is the lime scale which forms in pipes, heaters and on cooking utensils. Burn harzard. Hot water discharge.
NOTE: Un•Lime is not available for use in Canada. Hydrochloric base acids are not recommended for use on glass lined tanks. Chemical Hazard Observe handling instructions on label of product being used. Tank Cleanout Procedure • Product contains phosphoric acid. The following practices will ensure longer life and enable the unit to operate at its designed efficiency: • Keep out of reach of children. 1. 2. • Use rubber or neoprene gloves. Once a month the heater should be flushed.
9. and pour the UN•LIME into the heater. Install the long plastic male adapter insert fitting into the drain valve opening of heater after applying Teflon tape or paste to threads. Tighten firmly by hand and use wrench or adjustable pliers to check for secure connection. Do not over tighten to avoid damage to threads and fittings. Prepare the Up-N-Down Transfer Kit The next step is the preparation on the Up-N-Down Transfer Kit, if you have not already done so: 1.
For Your Information Contact the local water heater supplier or service agency for further information concerning an Anode Replacement Kit and this chlorination treatment. Start Up Conditions Smoke/Odor It is not uncommon to experience a small amount of smoke and odor during the initial start-up. This is due to burning off of oil from metal parts, and will disappear in a short while.
Troubleshooting COMPLAINT CAUSE USER REMEDY Qualified Service Agency Thermostat set too low. Set thermostat dial to a higher temperature Upper and/or lower temperature probe out of calibration. Call qualified service agency *Insufficient hot water Thermostat set too low. *See WATER TEMPERATURE CONTROL WARNING (on page 12). Set thermostat dial to a higher temperature Upper and/or lower temperature probe out of calibration.
ALT. COLD WATER CONNECTION HOT WATER TO FIXTURES NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5.
HOT WATER TO FIXTURES ALTERNATE LOCATION NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5.
HOT WATER RETURN TEMPERED WATER OUTLET COLD HOT HOT WATER OUTLET NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
PIPE T&P TO OPEN DRAIN NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s).
PIPE T&P TO OPEN DRAIN NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
PIPE T&P TO OPEN DRAIN NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5. The water heater’s operating thermostat should be set 5 degrees F higher than the Tank Temperature Control.
PIPE T&P TO OPEN DRAIN HOT WATER TO FIXTURES DRAIN EXPANSION TANK COLD WATER SUPPLY TANK TEMPERATURE CONTROL CIRCULATING PUMP PRESSURE RELIEF VALVE TEMPERATURE & PRESSURE RELIEF VALVE ALTERNATE LOCATION NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4.
EXPANSION TANK COLD WATER SUPPLY HOT WATER RETURN HOT WATER TO FIXTURES PRE-HEATED WATER TO BOOSTER DRAIN BOOSTER HEATER WATER FLOW SWITCH TEMPERATURE GAGE CHECK VALVE FULL PORT BALL VALVE BOOSTER WATER RETURN TANK TEMPERATURE CONTROL CIRCULATING PUMP PRESSURE RELIEF VALVE TEMPERATURE & PRESSURE RELIEF VALVE BOOSTER WATER TO FIXTURES NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3.
PRE-HEATER PRE-HEATER MUST BE IDENTICAL HEATERS PIPE T&P TO OPEN DRAIN DRAIN BOOSTER RETURN (IF USED) EXPANSION TANK COLD WATER SUPPLY TANK TEMPERATURE CONTROL CIRCULATING PUMP PRESSURE RELIEF VALVE TEMPERATURE & PRESSURE RELIEF VALVE HOT OUTLET AT STORED TEMPERATURE BOOSTED WATER OUTLET TYPICAL BOOSTER HEATER PIPE T&P TO OPEN DRAIN NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3.
PIPE T&P TO OPEN DRAIN PIPE T&P TO OPEN DRAIN NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. PIPE T&P TO OPEN DRAIN HOT WATER TO FIXTURES WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS.
HEATER PIPE T&P TO OPEN DRAIN HEATER PIPE T&P TO OPEN DRAIN HEATER PIPE T&P TO OPEN DRAIN DRAIN TANK TEMPERATURE CONTROL CIRCULATING PUMP PRESSURE RELIEF VALVE ALT. COLD WATER CONNECTION EXPANSION TANK HOT WATER RETURN WATER FLOW SWITCH TEMPERATURE GAGE CHECK VALVE FULL PORT BALL VALVE COLD WATER SUPPLY LEGEND TEMPERATURE & PRESSURE RELIEF VALVE HOT WATER TO FIXTURES NOTES: 1. Preferred piping diagram. 2.
HEATER PIPE T&P TO OPEN DRAIN HEATER PIPE T&P TO OPEN DRAIN HEATER AOS STORAGE TANK HOT WATER TO FIXTURES NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5.
PIPE T&P TO OPEN DRAIN PIPE T&P TO OPEN DRAIN PIPE T&P TO OPEN DRAIN NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. FINISHED FLOOR HOT WATER TO FIXTURES WARNING: THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES; CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS.
HEATER HEATER PIPE T&P TO OPEN DRAIN HEATER PIPE T&P TO OPEN DRAIN PIPE T&P TO OPEN DRAIN NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit. However, local codes shall govern their usage. 4. The Tank Temperature Control should be wired to and control the pump between the water heater(s) and the storage tank(s). 5.
HEATER HEATER PIPE T&P TO OPEN DRAIN HEATER PIPE T&P TO OPEN DRAIN DRAIN AOS STORAGE TANK ALTERNATE LOCATION PIPE T&P TO OPEN DRAIN TANK TEMPERATURE CONTROL CIRCULATING PUMP PRESSURE RELIEF VALVE TEMPERATURE & PRESSURE RELIEF VALVE HOT WATER TO FIXTURES NOTES: 1. Preferred piping diagram. 2. The temperature and pressure relief valve setting shall not exceed pressure rating of any component in the system. 3. Service valves are shown for servicing unit.
Model Dimension "A" SBL95 199NE 76 SBL85 275NE(A) 76 SBL85 390NE(A) 76
Notes 50
Limited Warranty Limited Warranty State Water Heaters, the warrantor, extends the following LIMITED WARRANTY to the owner of this water heater. 1.
www.statewaterheaters.com 500 Tennessee Waltz Parkway, Ashland City, TN 37015 Tech Support: 800-527-1953 Parts: 800-433-2545 Copyright © 2012 State Water Heaters, All rights reserved.