7. Faults and remedies
Fault Cause Remedy
No display Battery voltage too low Pre-charge the battery
The external fuse in the
battery connection cable
has blown.
Replace the external fuse
Battery is not connected Unclamp all connections
Connect a (new) battery
with the correct polarity
Reconnect the solar module
and loads
1.
2.
3.
Battery is defective
Battery is connected with
the wrong polarity
Device may be defective;
Return device to specialist
dealer
Info LED flashes
red
Charging interrupted due to
excessive charging current
Charging automatically
continues as soon as the
charging current lies within
the permissible range
Optobus transfer faulty Repeat programming
Battery voltage too low Pre-charge the battery
Battery voltage too high Check installation
Load cannot be
operated or only
for a short time
+
info LED flashes
red
Load output is switched
off due to excessive load
current
Reduce load current, if
necessary switch off or
disconnect loads
Check loads
Load output is switched off
due to short circuit at load
output
Disconnect loads
Correct the cause of the
short circuit
Reconnect loads
1.
2.
3.
Load output is switched off
due to overheating of the
solar charge controller
The load output automati-
cally switches on again once
the solar charge controller
has cooled down
Improve the cooling air
circulation
Remove any other heat
sources
Check the conditions of use
and the mounting location